Digital inputs
Programmable digital inputs
4 (6)
Terminal number
18, 19, 27
1)
, 29
1)
, 32, 33,
Logic
PNP or NPN
Voltage level
0–24 V DC
Voltage level, logic'0' PNP
<
5 V DC
Voltage level, logic'1' PNP
>
10 V DC
Voltage level, logic '0' NPN
>
19 V DC
Voltage level, logic '1' NPN
<
14 V DC
Maximum voltage on input
28 V DC
Input resistance, R
i
approx. 4 k
Ω
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Digital output
Programmable digital/pulse outputs
2
Terminal number
27, 29
1)
Voltage level at digital/frequency output
0–24 V
Max. output current (sink or source)
40 mA
Max. load at frequency output
1 k
Ω
Max. capacitive load at frequency output
10 nF
Minimum output frequency at frequency output
0 Hz
Maximum output frequency at frequency output
32 kHz
Accuracy of frequency output
Max. error: 0.1% of full scale
Resolution of frequency outputs
12 bit
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Pulse inputs
Programmable pulse inputs
2
Terminal number pulse
29, 33
Max. frequency at terminal, 29, 33
110 kHz (push-pull driven)
Max. frequency at terminal, 29, 33
5 kHz (open collector)
Min. frequency at terminal 29, 33
4 Hz
Voltage level
see
Maximum voltage on input
28 V DC
Input resistance, R
i
approx. 4 k
Ω
Pulse input accuracy (0.1–1 kHz)
Max. error: 0.1% of full scale
Control card, 24 V DC output
Terminal number
12, 13
Max. load
200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.