88
Service Functions
Parameters 600 through 631
This parameter group contains functions useful for troubleshooting the
drive including operating data, data log and fault log.
It also has information on the nameplate data of the drive.
Function:
These parameters can be read out through the serial communication
port as well as on the control panel display.
Description of choice:
Parameter 600, Operating Hours
Shows the number of hours the drive has had power applied. The
value is saved every hour and when the power is removed. This
value cannot be reset.
Parameter 601, Hours Run
Shows the number of hours the drive has powered the motor. This
parameter can be reset in parameter 619, Reset of Hours Run
Counter. The value is saved every hour and when the power is
removed.
Parameter 602, kWh Counter
Shows the output power of the drive. The calculation is based on the
mean value in kWh over one hour. This value can be reset using
parameter 618, Reset of kWh Counter.
Parameter 603 Number of Power Ups.
Shows the number of times power has been applied to the drive.
Parameter 604, Number of Overtemperature Trips
Shows the number of overtemperature trips from the heatsink tempera-
ture sensor on the drive.
Parameter 605, Number of Overvoltage Trips
Shows the number of overvoltage trips from the sensor of DC link
voltage of the drive. The count is only taken when Alarm 7 Overvolt-
age is activated.
600-605 Operating Data Value:
Value:
Parameter
Description
Display
Unit
Range
Number
Operating Data:
Text
600
Operating Hours
(OPERATING HOURS)
Hours
0 through 130,000.0
601
Hours Run
(RUNNING HOURS)
Hours
0 through 130,000.0
602
kWh Counter
(KWH COUNTER)
kWh
-
603
Number of Power-ups
(POWER UPS)
Occurences
0 through 9999
604
Number of Overtemp Trips
(OVER TEMPS)
Occurences
0 through 9999
605
Number of Overvoltage Trips
(OVER VOLTS)
Occurences
0 through 9999