18
Typical Control Connections
Shown below are typical interfaces between the VLT 6000 and other
components in an HVAC system. The terminal numbers and the
functions of the terminals are identical on all VLT 6000s. An optional
relay card, not shown, can provide four additional Form C output
relays. The RS-485 connections allow direct communication through
91 (L1)
92 (L2)
93 (L3)
(U) 96
(V) 97
(W) 98
(AUX RELAY) 01
( AUX RELAY) 02
(AUX RELAY) 03
Fault Indication*
240 V AC, 2 A
(PE) 95
(RELAY) 04
(RELAY) 05
Run Indication*
30 V AC, 1 A
(COM A OUT) 39
(A OUT) 42
(A OUT) 45
Output Current Indication*
4 - 20 mA
88 (-)
89 (+)
99 (PE)
Motor
3 Phase
Power
Input
External
DC Bus
Connection
Output Speed Indication*
4 - 20 mA
Switch Mode
Power Supply
24 V DC
200 mA
+
-
(P RS-485) 68
(N RS-485) 69
(COM RS-485) 61
+
-
RS-485
SW2
SW3
5 V
10 V DC
17 mA
+
-
50 (+10 V OUT)
60 (A IN)
+10 V DC
0 - 10 V DC
Ref. Input*
0 - 10 V DC
Ref. Input*
4 - 20 mA
Ref. Input*
54 (A IN)
55 (COM A IN)
53 (A IN)
12 (+24 V OUT)
13 (+24 V OUT)
SW4
Preset Speed*
Setup Select*
Setup Select*
Reset*
Lockout*
Run/Stop*
Reverse*
Interlock*
16 (D IN)
17 (D IN)
18 (D IN)
19 (D IN)
20 (COM D IN)
27 (D IN)
29 (D IN)
32 (D IN)
33 (D IN)
0 V
RS-485
Interface
Typical* VLT 6000 Wiring
* The operation of all control inputs and outputs is programmable.
*
Typical terminal functions are shown.
the drive’s built-in serial communication protocols: Johnson Controls
Metasys
®
N2, Siemens System 600 FLN
®
, or VLT Software Dialog
®
.
LonWorks
®
and Profibus
®
are available through option cards that fit into
the relay output card location.