93
Relay Card Functions
Parameters 700 through 711
Parameters 700 through 711 are only activated if a relay option card is
installed in the drive. A relay card can be field installed in the drive if
desired.
Activation/deactivation can be programmed in parameters 701, 704,
707 and 710, Relay 6, 7, 8 and 9, ON Delay; and parameters 702,
705, 708 and 711 Relay 6, 7, 8 and 9, OFF Delay.
700
Relay 6, Function
(RELAY6 FUNCTION)
703
Relay 7, Function
(RELAY7 FUNCTION)
706
Relay 8, Function
(RELAY8 FUNCTION)
709
Relay 9, Function
(RELAY9 FUNCTION)
Function:
This output activates a relay.
Relay outputs 6, 7, 8 and 9 can be used for showing status and
warnings. The relay is activated when the conditions for the relevant
data values have been fulfilled. Because these have the same possible
functions as relay 1, see the description under parameter 323.
701
Relay 6, ON Delay
(RELAY6 ON DELAY)
704
Relay 7, ON Delay
(RELAY7 ON DELAY)
707
Relay 8, ON Delay
(RELAY8 ON DELAY)
710
Relay 9, ON Delay
(RELAY9 ON DELAY)
Value:
0 to 600 sec.
★
0 sec.
Function:
This parameter allows a delay of the activation of relays 6, 7, 8 and 9
(terminals 1, and 2).
Description of choice:
Enter the desired value.
702
Relay 6, OFF Delay
(RELAY6 OFF DELAY)
705
Relay 7, OFF Delay
(RELAY7 OFF DELAY)
708
Relay 8, OFF Delay
(RELAY8 OFF DELAY)
711
Relay 9, OFF Delay
(RELAY9 OFF DELAY)
Value:
0 to 600 sec.
★
0 sec.
Function:
This parameter is used to delay the deactivation time of relays 6, 7, 8
and 9 (terminals 1 and 2).
Description of choice:
Enter the desired value.
This parameter allows a delay of the activation of relays 6, 7, 8 and 9
(terminals 1, and 2).
✭
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
Electrical Installation of the Relay Card
The relays are connected as shown below.
To achieve double isolation, mount the plastic foil as shown below.
Relay 6-9
A-B make, A-C break
Max. 240 VAC, 2 Amp