380 to 575 VAC Auxiliary Control Panel Tightening Torques
Max. Drive
Output Current
Overload
Relay
Power Terminal
Blocks
Circuit
Breaker
Disconnect or
Transfer Switch
Main or
Bypass Fuse
Block
Drive Fuse
Block
Ground
Terminal
to 6.6
15 (1.7)
15 (1.7)
22 (2.5)
7 (0.8)
20 (2.3)
35 (4.0)
45 (5.1)
7.5
15 (1.7)
15 (1.7)
22 (2.5)
7 (0.8)
25 (2.8)
35 (4.0)
45 (5.1)
10.6
15 (1.7)
15 (1.7)
22 (2.5)
7 (0.8)
25 (2.8)
35 (4.0)
45 (5.1)
16.7
15 (1.7)
15 (1.7)
22 (2.5)
7 (0.8)
25 (2.8)
35 (4.0)
45 (5.1)
24.2
15 (1.7)
50 (5.7)
22 (2.5)
7 (0.8)
45 (5.1)
45 (5.1)
45 (5.1)
30.8
15 (1.7)
50 (5.7)
22 (2.5)
7 (0.8)
120 (13.6)
45 (5.1)
45 (5.1)
46
75 (8.5)
50 (5.7)
44 (5.0)
18 (2.0)
120 (13.6)
120 (13.6)
45 (5.1)
61.2
75 (8.5)
275 (31.1)
44 (5.0)
18 (2.0)
120 (13.6)
275 (31.1)
50 (5.6)
74.8
120 (13.6)
275 (31.1)
44 (5.0)
18 (2.0)
120 (13.6)
275 (31.1)
50 (5.6)
88
120 (13.6)
275 (31.1)
44 (5.0)
70 (8.0)
120 (13.6)
275 (31.1)
50 (5.6)
115
120 (13.6)
275 (31.1)
44 (5.0)
375 (42.4)
275 (31.1)
150 (16.9)
50 (5.6)
143
250 (28.3)
275 (31.1)
50 (5.6)
375 (42.4)
275 (31.1)
150 (16.9) 120 (13.6)
169
275 (31.4)
275 (31.1)
50 (5.6)
375 (42.4)
275 (31.1)
150 (16.9) 150 (16.9)
All current ratings are in amps. All torques are in in-lbs (Nm). All TB1 connections must be torqued to 8 in-lbs (0.9 Nm).
200 to 240 VAC Auxiliary Control Panel Tightening Torques
200 to 240 VAC Terminal Tightening Torque
380 to 460 VAC Terminal Tightening Torque
Max. Drive
Output Current
Torque
in-lbs (Nm)
6.6
5 (0.6)
7.5
5 (0.6)
10.6
5 (0.6)
16.7
5 (0.6)
24.2
17 (1.8)
30.8
17 (1.8)
46.2
28 (3.0)
59.4
28 (3.0)
74.8
28 (3.0)
88
35 (4.0)
114
100 (11.3)
143
100 (11.3)
169
100 (11.3)
Max. Drive
Output Current
Torque
in-lbs (Nm)
Max. Drive
Output Current
Torque
in-lbs (Nm)
to 10
5 (0.6)
147
100 (11.3)
16
5 (0.6)
177
100 (11.3)
24
17 (1.8)
212
100 (11.3)
32
17 (1.8)
260
100 (11.3)
37.5
17 (1.8)
315
100 (11.3)
44
28 (3.0)
368
100 (11.3)
61
28 (3.0)
487
372 (42.0)
73
28 (3.0)
594
372 (42.0)
90
28 (3.0)
649
372 (42.0)
106
100 (11.3)
746
372 (42.0)
Terminal Tightening Torque
Tighten terminals connecting the drive input power, output to the motor(s)
and ground to the values shown in the tables below. Drives with 200 to
240 volts of 88 amps and less, and drives with 380 to 575 volts of 90 amps
and less, have removable terminal blocks with screws. Larger drives have
fixed bolts. (See the drive nameplate for maximum drive output current.)
Max. Drive
Output Current
Overload
Relay
Power Terminal
Blocks
Circuit
Breaker
Disconnect or
Transfer Switch
Main or
Bypass Fuse
Block
Drive Fuse
Block
Ground
Terminal
10
15 (1.7)
15 (1.7)
22 (2.5)
7 (0.8)
20 (2.3)
25 (2.8)
45 (5.1)
16
15 (1.7)
15 (1.7)
22 (2.5)
7 (0.8)
25 (2.8)
25 (2.8)
45 (5.1)
24
75 (8.5)
15 (1.7)
22 (2.5)
7 (0.8)
25 (2.8)
45 (5.1)
45 (5.1)
32
75 (8.5)
35 (4.0)
22 (2.5)
7 (0.8)
45 (5.1)
45 (5.1)
45 (5.1)
37.5
75 (8.5)
35 (4.0)
22 (2.5)
18 (2.0)
45 (5.1)
45 (5.1)
45 (5.1)
44
75 (8.5)
50 (5.6)
44 (5.0)
18 (2.0)
45 (5.1)
120 (13.6)
45 (5.1)
61
75 (8.5)
110 (12.5)
44 (5.0)
18 (2.0)
120 (13.6)
120 (13.6)
50 (5.6)
73
75 (8.5)
110 (12.5)
44 (5.0)
55 (6.2)
120 (13.6)
275 (31.1)
50 (5.6)
90
75 (8.5)
110 (12.5)
44 (5.0)
70 (8.0)
120 (13.6)
275 (31.1)
50 (5.6)
106
120 (13.6)
110 (12.5)
50 (5.6)
375 (42.4)
275 (31.1)
150 (16.9)
50 (5.6)
147
250 (28.3)
275 (31.1)
50 (5.6)
375 (42.4)
275 (31.1)
150 (16.9) 120 (13.6)
177
275 (31.1)
275 (31.1)
50 (5.6)
375 (42.4)
275 (31.1)
150 (16.9) 150 (16.9)
212
275 (31.1)
275 (31.1)
50 (5.6)
375 (42.4)
450 (50.8)
275 (31.1) 150 (16.9)
260
275 (31.1)
275 (31.1)
375 (42.4)
500 (56.5)
450 (50.8)
275 (31.1) 150 (16.9)
315
375 (42.4)
375 (42.4)
375 (42.4)
500 (56.5)
450 (50.8)
275 (31.1) 150 (16.9)
368
375 (42.4)
375 (42.4)
375 (42.4)
375 (42.4)
375 (42.4)
275 (31.1) 150 (16.9)
NOTE
Tighten terminals of 575 volt drives of 32 amps
and below to 17 in-lbs (1.8 Nm), and above 32
amps to 28 in-lbs (3.0 Nm).
All current ratings are in amps.