33
✭
Indicates default parameter. Depending upon the application, the drive may be delivered with other parameters selected.
Function:
See the functional description for parameter 008, Small Display
Readout.
Description of choice:
There is a choice of 26 meters, see parameter 007 Large Display
Readout.
010
Small Display Readout 1.3
(SMALL READOUT 3)
Value:
See parameter 007 Large Display Readout
★
Power [HP]
Function:
See the functional description for parameter 008 Small Data Readout.
Description of choice:
There is a choice of 26 different data values, see parameter 007 Large
Display Readout.
011
Unit of Local Reference (UNIT OF LOC REF)
Value:
Hz (HZ)
[0]
★
% of output frequency range (%) (% OF FMAX) [1]
Function:
This parameter sets the unit that will be displayed in Display Mode IV
when the drive’s speed is being controlled locally.
Description of choice:
Choose the desired unit for local reference.
012
Hand Start on LCP (HAND START BUTTON)
Value:
Disable (DISABLE)
[0]
★
Enable (ENABLE)
[1]
Function:
This parameter allows disabling the Hand/Start key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Hand/Start key will be
disabled.
013
OFF/STOP on LCP (STOP BUTTON)
Value:
Disable (DISABLE)
[0]
★
Enable (ENABLE)
[1]
Function:
This parameter allows disabling the Off/Stop key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Off/Stop key will be disabled.
CAUTION
!
If
Disable is selected, motor cannot be stopped
by Off/Stop key.
014
Auto Start on LCP
(AUTO START BTTN)
Value
Disable (DISABLE)
[0]
★
Enable (ENABLE)
[1]
Function:
This parameter allows disabling the Auto/Start key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Auto/Start key will be
disabled.
P
015
015
Reset on LCP
(RESET BUTTON)
Value:
Disable (DISABLE)
[0]
★
Enable (ENABLE)
[1]
Function:
This parameter allows disabling the Reset key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Reset key will be inactive.
CAUTION
!
Do not disable Reset unless a remote reset is
available through digital inputs and parameters
300 through 307.
016
Lock for Data Change (DATA CHANGE LOCK)
Value:
★
Not Locked (NOT LOCKED)
[0]
Locked (LOCKED)
[1]
Function:
This parameter allows locking out parameter changes at the local
control panel.
Description of choice:
If Locked is selected, data modifications in the parameters cannot be
made. Parameter changes will be possible through serial communica-
tion.
Parameters 007 through 010, Display Readout can be changed at the
local control panel.
The local control panel can also be locked or unlocked by a digital
input controlled by parameters 300 through 307.