mains supply 3 x 525 - 690 V
According to international requirements
VLT type 5122
5152
5202
5252
5302
5352
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (525-550 V)
162
201
253
303
360
418
I
VLT, MAX
(60 s) [A]
(525-550 V)
178
221
278
333
396
460
I
VLT,N
[A] (551-690 V)
155
192
242
290
344
400
I
VLT, MAX
(60 s) [A]
(551-690 V)
171
211
266
319
378
440
Output
S
VLT,N
[kVA] (550 V)
154
191
241
289
343
398
S
VLT,N
[kVA] (575 V)
154
191
241
289
343
398
S
VLT,N
[kVA] (690 V)
185
229
289
347
411
478
Typical shaft output
[kW] (550 V)
110
132
160
200
250
315
[HP]
(575
V)
150
200
250
300
350
400
[kW] (690 V)
132
160
200
250
315
400
High overload torque (160 %):
Output current
I
VLT,N
[A] (525-550 V)
137
162
201
253
303
360
I
VLT, MAX
(60 s) [A]
(525-550 V)
206
243
302
380
455
540
I
VLT,N
[A] (551-690 V)
131
155
192
242
290
344
I
VLT, MAX
(60 s) [A]
(551-690 V)
197
233
288
363
435
516
Output
S
VLT,N
[kVA] (550 V)
131
154
191
241
289
343
S
VLT,N
[kVA] (575 V)
130
154
191
241
289
343
S
VLT,N
[kVA] (690 V)
157
185
229
289
347
411
Typical shaft output
[kW] (550 V)
90
110
132
160
200
250
[HP]
(575
V)
125
150
200
250
300
350
[kW] (690 V)
110
132
160
200
250
315
Max. cable cross-section
to motor
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Max. cable cross-section
to loadsharing and brake
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Normal overload torque (110 %):
Rated input current
I
L,N
[A] (550 V)
158
198
245
299
355
408
I
L,N
[A] (575 V)
151
189
234
286
339
390
I
L,N
[A] (690 V)
155
197
240
296
352
400
High overload torque (160 %):
Rated input current
I
L,N
[A] (550 V)
130
158
198
245
299
355
I
L,N
[A] (575 V)
124
151
189
234
286
339
I
L,N
[A] (690 V)
128
155
197
240
296
352
Max. cable cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Max. pre-fuses (mains)
[-]/UL
[A]
1
315
350
350
400
500
550
Efficiency
3
0,98
Power loss
Normal overload [W] 3114
3612
4292
5155
5821
6149
High overload [W] 2664
2952
3451
4275
4875
5185
Weight
IP 00 [kg]
82
91
112
123
138
151
Weight
IP 21/Nema1 [kg]
96
104
125
136
151
165
Weight
IP 54/Nema12 [kg]
96
104
125
136
151
165
Enclosure
IP 00, IP 21/Nema 1 and IP 54/Nema12
1. For type of fuse see section
Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with
national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply and motor: M10; Brake and loadsharing: M8
VLT
®
5000 Design Guide
52
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark