Compact, Mains supply 3 x 380 - 500 V
According to international requirements
VLT type
5016
5022
5027
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (380-415 V)
32
37.5
44
I
VLT, MAX
(60 s) [A] (380-415 V)
35.2
41.3
48.4
I
VLT,N
[A] (440-500 V)
27.9
34
41.4
I
VLT, MAX
(60 s) [A] (440-500 V)
30.7
37.4
45.5
Output
S
VLT,N
[kVA] (380-415 V)
24.4
28.6
33.5
S
VLT,N
[kVA] (440-500 V)
24.2
29.4
35.8
Typical shaft output
P
VLT,N
[kW]
15
18.5
22
Typical shaft output
P
VLT,N
[HP]
20
25
30
High overload torque (160 %):
Output current
I
VLT,N
[A] (380-415 V)
24
32
37.5
I
VLT, MAX
(60 s) [A] (380-415 V)
38.4
51.2
60
I
VLT,N
[A] (440-500 V)
21.7
27.9
34
I
VLT, MAX
(60 s) [A] (440-500 V)
34.7
44.6
54.4
Output
S
VLT,N
[kVA] (380-415 V)
18.3
24.4
28.6
S
VLT,N
[kVA] (440-500 V)
18.8
24.2
29.4
Typical shaft output
P
VLT,N
[kW]
11
15
18.5
Typical shaft output
P
VLT,N
[HP]
15
20
25
Max. cable cross-section to motor,
IP 54
16/6
16/6
16/6
brake and loadsharing [mm
2
]/[AWG]
2)
IP 20
16/6
16/6
35/2
Min. cable cross-section to motor,
brake and loadsharing [mm2]/[AWG]
2) 4)
10/8
10/8
10/8
Rated input current
I
L,N
[A] (380 V)
32
37.5
44
I
L,N
[A] (460 V)
27.6
34
41
Max. cable cross-section,
IP 54
16/6
16/6
16/6
power [mm
2
]/[AWG]
IP 20
16/6
16/6
35/2
Max. pre-fuses
[-]/UL
1)
[A]
63/40
63/50
63/60
Efficiency
3)
0.96
0.96
0.96
Weight IP 20 EB
[kg]
21
22
27
Weight IP 54
[kg]
41
41
42
Power loss at max. load.
- high overload torque (160 %)
[W]
419
559
655
- normal overload torque (110 %)
[W]
559
655
768
Enclosure
IP 20/
IP 54
IP 20/
IP 54
IP 20/
IP 54
1. For type of fuse see section
Fuses.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply
with national and local regulations on min. cable cross-section.
VLT
®
5000 Design Guide
42
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark