Compact, Mains supply 3 x 525 - 600 V
According to international requirements
VLT type 5001
5002
5003
5004
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (550 V)
2.6
2.9
4.1
5.2
I
VLT, MAX
(60 s) [A] (550 V)
2.9
3.2
4.5
5.7
I
VLT,N
[A] (575 V)
2.4
2.7
3.9
4.9
I
VLT, MAX
(60 s) [A] (575 V)
2.6
3.0
4.3
5.4
Output
S
VLT,N
[kVA] (550 V)
2.5
2.8
3.9
5.0
S
VLT,N
[kVA] (575 V)
2.4
2.7
3.9
4.9
Typical shaft output
P
VLT,N
[kW]
1.1
1.5
2.2
3
Typical shaft output
P
VLT,N
[HP]
1.5
2
3
4
Highl overload torque (160%):
Output current
I
VLT,N
[A] (550 V)
1.8
2.6
2.9
4.1
I
VLT, MAX
(60 s) [A] (550 V)
2.9
4.2
4.6
6.6
I
VLT,N
[A] (575 V)
1.7
2.4
2.7
3.9
I
VLT, MAX
(60 s) [A] (575 V)
2.7
3.8
4.3
6.2
Output
S
VLT,N
[kVA] (550 V)
1.7
2.5
2.8
3.9
S
VLT,N
[kVA] (575 V)
1.7
2.4
2.7
3.9
Typical shaft output
P
VLT,N
[kW]
0.75
1.1
1.5
2.2
Typical shaft output
P
VLT,N
[HP]
1
1.5
2
3
Max. cable cross-section to motor,
brake and loadsharing [mm
2
]/[AWG]
2)
4/10
4/10
4/10
4/10
Normal overload torque (110 %):
Rated input current
I
L,N
[A] (550 V)
2.5
2.8
4.0
5.1
I
L,N
[A] (600 V)
2.2
2.5
3.6
4.6
High overload torque ( 160 %):
Rated input current
I
L,N
[A] (550 V)
1.8
2.5
2.8
4.0
I
L,N
[A] (600 V)
1.6
2.2
2.5
3.6
Max. cable cross-section, power [mm
2
]/[AWG]
2)
4/10
4/10
4/10
4/10
Max. pre-fuses
[-]/UL
1)
[A]
3
4
5
6
Efficiency
3)
0.96
0.96
0.96
0.96
Weight IP 20 EB
[kg]
10.5
10.5
10.5
10.5
Power loss at max.
load.
[W]
63
71
102
129
Enclosure
IP 20 / Nema 1
1. For type of fuses see section
Fuses
.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
VLT
®
5000 Design Guide
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark
47