PNU
#
Parameter description
Factory setting
Range
Changes
during
operation 4-Setup
Conversion
index
Data
type
300
Terminal 16, input
Reset
Yes
Yes
0
5
301
Terminal 17, input
Freeze reference
Yes
Yes
0
5
302
Terminal 18 Start, input
Start
Yes
Yes
0
5
303
Terminal 19, input
Reversing
Yes
Yes
0
5
304
Terminal 27, input
Coasting stop, inverse
Yes
Yes
0
5
305
Terminal 29, input
Jog
Yes
Yes
0
5
306
Terminal 32, input
Choice of setup, msb/speed up
Yes
Yes
0
5
307
Terminal 33, input
Choice of setup, lsb/speed down
Yes
Yes
0
5
308
Terminal 53, analogue input voltage
Reference
Yes
Yes
0
5
309
Terminal 53, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
310
Terminal 53, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
311
Terminal 54, analogue input voltage
No operation
Yes
Yes
0
5
312
Terminal 54, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
313
Terminal 54, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
314
Terminal 60, analogue input current
Reference
Yes
Yes
0
5
315
Terminal 60, min. scaling
0.0 mA
0.0 - 20.0 mA
Yes
Yes
-4
5
316
Terminal 60, max. scaling
20.0 mA
0.0 - 20.0 mA
Yes
Yes
-4
5
317
Time out
10 sec.
1 - 99 sec.
Yes
Yes
0
5
318
Function after time out
Off
Yes
Yes
0
5
319
Terminal 42, output
0 - I
MAX
Þ 0-20 mA
Yes
Yes
0
5
320
Terminal 42, output, pulse scaling
5000 Hz
1 - 32000 Hz
Yes
Yes
0
6
321
Terminal 45, output
0 - f
MAX
Þ 0-20 mA
Yes
Yes
0
5
322
Terminal 45, output, pulse scaling
5000 Hz
1 - 32000 Hz
Yes
Yes
0
6
323
Relay 01, output
Ready - no thermal warning
Yes
Yes
0
5
324
Relay 01, ON delay
0.00 sec.
0.00 - 600 sec.
Yes
Yes
-2
6
325
Relay 01, OFF delay
0.00 sec.
0.00 - 600 sec.
Yes
Yes
-2
6
326
Relay 04, output
Ready - remote control
Yes
Yes
0
5
327
Pulse reference, max. frequency
5000 Hz
Yes
Yes
0
6
328
Pulse feedback, max. frequency
25000 Hz
Yes
Yes
0
6
329
Encoder feedback pulse/rev.
1024 pulses/rev.
1 - 4096 pulses/
rev.
Yes
Yes
0
6
330
Freeze reference/output function
No operation
Yes
No
0
5
345
Encoder loss timeout
1 sec.
0 - 60 sec
Yes
Yes
-1
6
346
Encoder loss function
OFF
Yes
Yes
0
5
357
Terminal 42, Output minimum scaling
0 %
000 - 100%
Yes
Yes
0
6
358
Terminal 42, Output maximum scaling
100%
000 - 500%
Yes
Yes
0
6
359
Terminal 45, Output minimum scaling
0 %
000 - 100%
Yes
Yes
0
6
360
Terminal 45, Output maximum scaling
100%
000 - 500%
Yes
Yes
0
6
361
Encoder loss threshold
300%
000 - 600 %
Yes
Yes
0
6
VLT
®
5000 Design Guide
134
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark