Compact, Mains supply 3 x 380 - 500 V
According to international requirements
VLT type 5352
5452
5502
5552
Normal overload current (110 %):
Output current
I
VLT,N
[A] (380-415 V) 600
658
745
800
I
VLT, MAX
(60 s) [A] (380-415
V)
660
724
820
880
I
VLT,N
[A] (440-500 V) 540
590
678
730
I
VLT, MAX
(60 s) [A] (440-500
V)
594
649
746
803
Output
S
VLT,N
[kVA] (400 V) 416
456
516
554
S
VLT,N
[kVA] (460 V) 430
470
540
582
S
VLT,N
[kVA] (500 V) 468
511
587
632
Typical shaft output
[kW] (400 V) 315
355
400
450
[HP] (460 V) 450
500
550/600
600
[kW] (500 V) 355
400
500
530
High overload torque (160 %):
Output current
I
VLT,N
[A] (380-415 V) 480
600
658
695
I
VLT, MAX
(60 s) [A] (380-415
V)
720
900
987
1042
I
VLT,N
[A] (440-500 V) 443
540
590
678
I
VLT, MAX
(60 s) [A] (440-500
V)
665
810
885
1017
Output
S
VLT,N
[kVA] (400 V) 333
416
456
482
S
VLT,N
[kVA] (460 V) 353
430
470
540
S
VLT,N
[kVA] (500 V) 384
468
511
587
Typical shaft output
[kW] (400 V) 250
315
355
400
[HP] (460 V) 350
450
500
550
[kW] (500 V) 315
355
400
500
Max. cable cross-section
to motor and loadsharing
[mm
2
]
4,6
[AWG]
2,4,6
4x240
4x500 mcm
Max. cable cross-section
to brake
[mm
2
]
4,6
[AWG]
2,4,6
2x185
2x350 mcm
Normal overload current (110 %):
Rated input current
I
L,N
[A] (380-415 V) 590
647
733
787
I
L,N
[A] (440-500 V) 531
580
667
718
High overload torque (160 %):
Rated input current
I
L,N
[A] (380-415 V) 472
590
647
684
I
L,N
[A] (440-500 V) 436
531
580
667
Max. cable cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
4x240
4x500 mcm
Max. pre-fuses (mains)
[-]/UL
[A]
1
700/700
900/900
900/900
900/900
Efficiency
3
0,98
Power loss
Normal overload [W] 7630
7701
8879
9428
High overload [W] 6005
6960
7691
7964
Weight
IP 00 [kg] 221
234
236
277
Weight
IP 21/Nema1 [kg] 263
270
272
313
Weight
IP 54/Nema12 [kg] 263
270
272
313
Enclosure
IP 00, IP 21/Nema 1 and IP 54/Nema12
1. For type of fuse see section
Fuses
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with
national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply, motor and loadsharing: M10 (compression lug), 2xM8 (box lug), M8 (brake)
VLT
®
5000 Design Guide
46
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark