PN
U # Parameter description
Factory setting
Range
Changes
during
operation
4-Setup
Conversion
index
Data
type
430 F 4 frequency
parameter 104
par.426-par.432
Yes
Yes
-1
6
431 U 5 voltage
parameter 103
.0 - U
VLT, MAX
Yes
Yes
-1
6
432 F 5 frequency
parameter 104
par.426 - 1000 Hz
Yes
Yes
-1
6
433 Torque proportional gain
100%
0 (Off) - 500%
Yes
Yes
0
6
434 Torque integral time
0.02 sec.
0.002 - 2.000 sec.
Yes
Yes
-3
7
437 Process PID Normal/inverse control
Normal
Yes
Yes
0
5
438 Process PID anti windup
On
Yes
Yes
0
5
439 Process PID start frequency
parameter 201
f
min - fmax
Yes
Yes
-1
6
440 Process PID proportional gain
0.01
0.00 - 10.00
Yes
Yes
-2
6
441 Process PID integral time
9999.99 sec. (OFF)
0.01 - 9999.99 sec.
Yes
Yes
-2
7
442 Process PID differentiation time
0.00 sec. (OFF)
0.00 - 10.00 sec.
Yes
Yes
-2
6
443 Process PID diff. gain limit
5.0
5.0 - 50.0
Yes
Yes
-1
6
444 Process PID lowpass filter time
0.01
0.01 - 10.00
Yes
Yes
-2
6
445 Flying start
Disable
Yes
Yes
0
5
446 Switching pattern
SFAVM
Yes
Yes
0
5
447 Torque compensation
100%
-100 - +100%
Yes
Yes
0
3
448 Gear ratio
1
0.001 - 100.000
No
Yes
-2
4
449 Friction loss
0%
0 - 50%
No
Yes
-2
6
450 Mains voltage at mains fault
Depends on unit
Depends on unit
Yes
Yes
0
6
453 Speed closed loop gear ratio
1
0.01-100
No
Yes
0
4
454 Dead time compensation
On
No
No
0
5
455 Frequency range monitor
Enable
0
5
457 Phase loss function
Trip
Yes
Yes
0
5
483 Dynamic DC Link compensation
On
No
No
0
5
VLT
®
5000 Design Guide
136
MG.52.B2.02 - VLT
®
is a registered Danfoss trademark