7.3.11 VLT
®
Extended Relay Card MCB 113
The MCB 113 adds 7 digital inputs, 2 analog outputs, and
4 SPDT relays to the standard I/O of the frequency
converter, providing increased flexibility and compliance
with the German NAMUR NE37 recommendations.
The MCB 113 is a standard C1-option for the Danfoss VLT
®
AutomationDrive FC 302 and is detected automatically
after mounting.
130BA965.10
12
11
10
9
8
7
6
5
4
3
2
1
4
3
2
1
12
11
10
9
8
7
6
5
4
3
2
1
2
1
13 14
+
- + -
+
-
+
- + - + - + - + - + - + -
A03
A03
Ex
t. 24
VDC
DI1
DI2
DI3
DI4
DI5
DI6
DI7
X45/
X48/
X46/
X47/
Rela
y 3
Rela
y 4
Rela
y 5
Rela
y 6
Illustration 7.17 Electrical Connections of MCB 113
Ensure galvanic isolation between the VLT
®
Automa-
tionDrive and the option card MCB 113 by connecting to
an external 24 V on X58/. If galvanic isolation is not
needed, the option card can be powered through internal
24 V from the frequency converter.
NOTICE
It is acceptable to combine 24 V signals with high-
voltage signals in the relays as long as there is 1 unused
relay in-between.
To set up MCB 113, use
parameter groups 5-1* Digital
Inputs
,
6-7* Analog Output 3
,
6-8* Analog Output 4
,
14-8*
Options
,
5-4* Relays
, and
16-6* Inputs and Outputs
.
NOTICE
In
parameter group 5-4* Relays
, array [2] is relay 3, array
[3] is relay 4, array [4] is relay 5, and array [5] is relay 6.
Electrical data
Relays
Numbers
4 SPDT
Load at 250 V AC/30 V DC
8A
Load at 250 V AC/30 V DC with cosφ = 0.4
3.5 A
Overvoltage category (contact-earth)
III
Overvoltage category (contact-contact)
II
Combination of 250 V and 24 V signals
Possible with 1 unused relay in between
Maximum thru-put delay
10 ms
Isolated from ground/ chassis for use on IT mains systems
Digital Inputs
Numbers
7
Range
0/24 V
Mode
PNP/NPN
Input impedance
4 kW
Low trigger level
6.4 V
High trigger level
17 V
Maximum through-put delay
10 ms
Analog Outputs
Numbers
2
Range
0/4-20 mA
Resolution
11 bit
Linearity
<0.2%
EMC
EMC
IEC 61000-6-2 and IEC 61800-3 regarding Immunity of BURST, ESD, SURGE, and Conducted Immunity