Power range
N315
N400
N450
N500
N560
N630
Drive modules
2
2
2
2
2
2
Rectifier configuration
12-pulse
High/normal load
NO
NO
NO
NO
NO
NO
Typical shaft output at 525–550 V [kW]
250
315
355
400
450
500
Typical shaft output at 575 V [hp]
350
400
450
500
600
650
Typical shaft output at 690 V [kW]
315
400
450
500
560
630
Protection rating
IP00
Efficiency
0.98
Output frequency [Hz]
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
Power card ambient trip [°C (°F)]
80 (176)
Output current [A]
Continuous (at 550 V)
360
418
470
523
596
630
Intermittent (60 s overload) at 550 V
396
360
517
575
656
693
Continuous (at 575/690 V)
344
400
450
500
570
630
Intermittent (60 s overload) at 575/690 V
378
440
495
550
627
693
Continuous (at 550 V) kVA
343
398
448
498
568
600
Continuous (at 575 V) kVA
343
398
448
498
568
627
Continuous (at 690 V) kVA
411
478
538
598
681
753
Input current [A]
Continuous (at 550 V)
355
408
453
504
574
607
Continuous (at 575 V)
339
490
434
482
549
607
Continuous (at 690 V)
352
400
434
482
549
607
Power losses [W]
Drive modules at 575 V
4401
4789
5457
6076
6995
7431
Drive modules at 690 V
4352
4709
5354
5951
6831
7638
AC busbars at 575 V
540
541
544
546
550
553
DC busbars during regeneration
88
88.5
90
91
186
191
Maximum cable size [mm
2
(mcm)]
Mains
1)
2x120 (250)
4x120 (250)
Motor
2x120 (250)
4x120 (250)
Brake
4x70 (2/0)
4x95 (3/0)
Regeneration terminals
4x120 (250)
Maximum external mains fuses
700 V, 550 A
700 V, 630 A
Table 6.4 FC 102, 525–690 V AC Mains Supply (2-Drive System)
1) For 12-pulse units, the cables between the star and delta terminals must be equal in number and length.
Specifications
Design Guide
MG37N102