17.6 Speed Up/Down
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB804.10
Function
Setting
Parameter 5-10 T
erminal 18
Digital Input
[8] Start*
Parameter 5-12 T
erminal 27
Digital Input
[19] Freeze
Reference
parameter 5-13 T
erminal 29
Digital Input
[21] Speed Up
Parameter 5-14 T
erminal 32
Digital Input
[22] Speed
Down
*=Default value
Notes/comments:
Table 17.10 Speed Up/Down
Start (18)
Freeze ref (27)
Speed up (29 )
Speed down (32 )
Speed
Reference
130BB840.11
Illustration 17.3 Speed Up/Down
17.7 RS485 Network Connection
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10 V
A IN
A IN
COM
A OUT
COM
R1
R2
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
01
02
03
04
05
06
-
61
68
69
RS-485
+
130BB685.10
Function
Setting
Parameter 8-30 P
rotocol
FC*
Parameter 8-31 A
ddress
1*
Parameter 8-32 B
aud Rate
9600*
*=Default value
Notes/comments:
Select protocol, address, and
baud rate in the parameters.
Table 17.11 RS485 Network Connection
Application Examples
Design Guide
MG37N102