Connect a large surface of the shield to ground,
for example with a cable clamp or a conductive
cable gland.
•
Maintain the same ground potential throughout
the network by applying potential-equalizing
cables.
•
Prevent impedance mismatch by using the same
type of cable throughout the entire network.
Cable
Shielded twisted pair (STP)
Impedance
120
Ω
Maximum cable length
Station-to-station [m
(ft)]
500 (1640)
Total including drop
lines [m (ft)]
1200 (3937)
Table 12.2 Cable Information
12.3 Relay Output
The relay terminal is on the top plate of the drive module.
Connect the relay terminal of drive module 1 (the drive
module on the far left) to the terminal blocks on the
control shelf using an extended wiring harness.
NOTICE
For reference, drive modules are numbered from left to
right.
Relay 1
•
Terminal 01: Common
•
Terminal 02: Normally open 400 V AC
•
Terminal 03: Normally closed 240 V AC
Relay 2
•
Terminal 04: Common
•
Terminal 05: Normally open 400 V AC
•
Terminal 06: Normally closed 240 V AC
Relay 1 and relay 2 are programmed in
parameter 5-40 Function Relay
,
parameter 5-41 On Delay,
Relay
, and
parameter 5-42 Off Delay, Relay
.
Use VLT
®
Relay Card MCB 105 option module for extra
relay outputs.
130BC554.
11
Relay 1
Relay 2
03
02
240 VAC, 2 A
01
06
05
04
240 VAC, 2 A
400 VAC, 2 A
400 VAC, 2 A
Illustration 12.5 Extra Relay Outputs
Control Wiring
VLT
®
Parallel Drive Modules
122
Danfoss A/S © 6/2016 All rights reserved.
MG37N102