12 Control Wiring
12.1 Control Cable Routing
Cable routing
Route the cable inside the drive cabinets as shown in
. Wire routing for a 2-drive configuration is identical,
except for the number of drive modules used.
•
Isolate the control wiring from the high-power components in the drive modules.
•
When the drive module is connected to a thermistor, ensure that the thermistor control wiring is shielded and
reinforced/double insulated. A 24 V DC supply voltage is recommended. See
130BF044.10
1
3
6
5
2
7
4
1
Microswitch cable
5
44-pin ribbon cable from MDCIC to drive module 4
2
Relay cable (shown connected to terminal on top of
module)
6
Bracket to support ribbon cable
3
44-pin ribbon cable from MDCIC to drive modules 1 and 2
7
Relay cable (shown connected to relay terminal on control shelf)
4
Ferrite core
–
–
Illustration 12.1 Control Cable Routing for a 4-Drive System