7.3.6 VLT
®
Encoder Input MCB 102
The encoder module can be used as a feedback source for closed-loop flux control (
parameter 1-02 Flux Motor Feedback
Source
) and closed-loop speed control (
parameter 7-00 Speed PID Feedback Source
). Configure the encoder option in
parameter group 17-** Motor Feedback Option
.
The Encoder Option MCB 102 is used for:
•
VVC
+
closed loop.
•
Flux vector speed control.
•
Flux vector torque control.
•
Permanent magnet motor.
Supported encoder types:
•
Incremental encoder: 5 V TTL type, RS422, maximum frequency: 410 kHz.
•
Incremental encoder: 1Vpp, sine-cosine.
•
HIPERFACE
®
Encoder: Absolute and Sine-Cosine (Stegmann/SICK).
•
EnDat encoder: Absolute and Sine-Cosine (Heidenheim) Supports version 2.1.
•
SSI encoder: Absolute.
NOTICE
The LEDs are only visible when removing the LCP. Reaction if there is an encoder error can be selected in
parameter 17-61 Feedback Signal Monitoring
:
[0] Disabled
,
[1] Warning
, or
[2] Trip
.
When the encoder option kit is ordered separately, the kit includes:
•
VLT
®
Encoder Input MCB 102.
•
Enlarged LCP fixture and enlarged terminal cover.
The encoder option does not support VLT
®
AutomationDrive FC 302 frequency converters manufactured before week
50/2004.
Minimum software version: 2.03 (
parameter 15-43 Software Version
)
Connector
Designation
X31
Incremental
encoder (refer
to
SinCos encoder
HIPERFACE
®
(refer to
)
EnDat encoder SSI encoder
Description
1
NC
24 V
1)
24 V Output (21–25 V, I
max
125 mA)
2
NC
8 VCC
8 V Output (7–12 V, I
max
: 200 mA)
3
5 VCC
5 VCC
5 V
1)
5 V Output (5 V ±5%, I
max
: 200 mA)
4
GND
GND
GND
GND
5
A input
+COS
+COS
A input
6
A inv input
REFCOS
REFCOS
A inv input
7
B input
+SIN
+SIN
B input
8
B inv input
REFSIN
REFSIN
B inv input
9
Z input
+Data RS485
Clock out
Clock out
Z input OR +Data RS485
10
Z inv input
-Data RS485
Clock out inv.
Clock out inv.
Z input OR -Data RS485
11
NC
NC
Data in
Data in
Future use
12
NC
NC
Data in inv.
Data in inv.
Future use
Max. 5 V on X31.5-12
Table 7.10 Encoder Option MCB 102 Terminal Descriptions for Supported Encoder Types
1) Supply for encoder: see data on encoder.
Ordering Information
VLT
®
Parallel Drive Modules
70