VFD500 high performance vector control frequency inverter user manual Chapter 7 Selection guide of inverter
Accessory
7.3 IO Extension card
◆
VFD500-IOEX1 Extension card
The VFD500-IOEX1 expansion card is a multi-function IO expansion card for VFD500 series inverters. It can expand 4
channels of DI, 2 channels of AI, and 4 channels of DO. Among them, AI4 can be used as ordinary voltage type input
analog quantity, and can also be used as PT100. Type or PT1000 type temperature detection input.
The terminal definitions of the VFD500-IOEX1 expansion card are shown in Table 7-10
Pin number diagram
Pin
number
Name
Usage
1
EXCLO
Resolver excitation negative
2
EXC
Resolver excitation positive
3
SIN
Resolver feedback SIN positive
4
SINLO
Resolver feedback SIN negative
5
COS
Resolver feedback COS positive
9
COSLO
Resolver feedback COS negative
6
,
7
,
8
NC
Hanging in air
(
PORT TYPE
:
DB9
)
Terminal distribution
SN
Te r m i n a l
name
Terminal function description
1
、
10
GND
Analog ground, internally isolated from COM
2
AI4
Analog input 4
Input 0~10V: input impedance 22K
Ω
3
、
6
、
16
COM
+24V, PT, PLC and digital input and output
public terminal
4
24V
Provides +24V power supply to the outside,
generally used as digital input and output terminal
working power supply and external sensor power
supply
5
PLC
Digital input power terminal
It is used for switching between high and low level
of switch input. It is short-circuited with +24V at the
factory, that is, DI is active at low level.
When the external power is input, disconnect the
PLC from the +24V.
It is a separate network from the PLC on the IO
board and is used separately.
Support PT100/PT1000/
KTY84-130
AI4 is inactive when using the
temperature sensor direct
c o n n e c t i o n f u n c t i o n
( t e m p e r a t u r e d e t e c t i o n
connection PT and COM)
Connect Control panel
122