Chapter 5 Function code VFD500 high performance vector control frequency inverter user manual
Function
code
Parameter name
Description
Default
Property
00Group Basic Function
P00.00
User password
0 ~ 65535
➢
No user password status after power-on
(P00.01=1):
The way to set a user password to lock is that
Entering the same non-zero value two tmes in
succession
➢
Locked staus
Enter the password to unlock
➢
Unlocked status
Enter the original password to lock inverter;
enter the same value twice in a row to change
the password (password will be cleared if you
enter 0 two times in a row).
0
☆
P00.01
Access authority
0
:
END USER
Some parameter are not authorized to check
when user password in locked state 1
:
Standard
ALL Parameter can be checked
1
●
P00.02
Parameter copy and
backup
0
:
No action
11
:
save all parameter to EEPROM backup
space
12
:
Restore all parameter from EEPROM
backup space
0
★
P00.03
RESET
0
:
NO ACTION
11
:
Restore default parameter except for
motor parameter and auto-tune related
parameter and factory parameter
12:Restore default to factory parameter
13
:
Clear tripping record
0
★
P00.04
Motor Control mode
0
:
VF
1
:
SVC(sensorless vector control)
➢
Open loop vector without encoder
feedback and the feedback speed is
internally estimated and supports torque
control mode.
2
:
VC Vector control with sensor
➢
Close loop vec tor and torque control
supporting encoder feedback in high
precision or torque control
application.The inverter must be
equipped with a PG card that matches
the encoder. For the relevant parameters
of the PG card, please refer to P10 group
0
★
P00.05
Running mode
0
:
Speed mode
1
:
Torque mode
➢
If use with DI function,19:Switch between
torque and speed Control and 20: torque
control diabled. Actuall effective running
mode is related with DI status
0
★
42