Chapter 5 Function code VFD500 high performance vector control frequency inverter user manual
P01.19
Multi-step speed
reference source
Unit’digit
:
0 phase reference source
set by
0-multi-step speed(P01.21)
1-preset frequency (P00.07)
2:AI1
3:AI2
4:AI3(IO expansion board)
5:AI4(IO expansion board)
6:HDI pulse
7:Communication
8:PID
Ten’s digit
:
Combination of multiple speed
0
:
Combination method
1
:
Priority method
00
★
Combination method Description:
Multispeed terminal 4
Multispeed terminal 3
Multispeed terminal 2
Multispeed terminal 1
Combination method Speed reference
Ineffective Ineffective Ineffective Ineffective Multispeed 0
Ineffective Ineffective Ineffective
effective
Multispeed 1
Ineffective Ineffective
effective
Ineffective Multispeed 2
Ineffective Ineffective
effective effective
Multispeed 3
Ineffective
effective
Ineffective Ineffective Multispeed 4
Ineffective
effective
Ineffective
effective
Multispeed 5
Ineffective
effective effective
Ineffective Multispeed 6
Ineffective
effective effective effective
Multispeed 7
effective
Ineffective Ineffective Ineffective Multispeed 8
effective
Ineffective Ineffective
effective
Multispeed 9
effective
Ineffective
effective
Ineffective Multispeed 10
effective
Ineffective
effective effective
Multispeed 11
effective effective
Ineffective Ineffective Multispeed 12
effective effective
Ineffective
effective
Multispeed 13
effective effective effective
Ineffective Multispeed 14
effective effective effective effective
Multispeed 15
Priority method Description:
Multispeed terminal 4
Multispeed terminal 3
Multispeed terminal 2
Multispeed terminal 1
Priority
method Speed reference
Ineffective Ineffective Ineffective Ineffective Multispeed 0
Ineffective Ineffective Ineffective
effective
Multispeed 1
Ineffective Ineffective
effective
random Multispeed 2
Ineffective
effective
random random Multispeed 3
effective
random random random Multispeed 4
Function
code
Parameter name
Description
Default
Property
Risk speed or Jump frequency start up protection is used to some situation which need avoid motor speed
and speed range,for example,due to mechanical resonance ,P01.12 will be enabled to avoide risk speed in
forward or reverse mode
。
Motor frequency
Giving frequency
P01.13
P01.15
P01.14
P01.17
P01.16
P01.18
46