Symbol
Index
Default
Value range
Tclpout
517
3000
1 to 30000 (ms)
Qth
518
0
0 to 100 (0.0 to 10.0 % of max port flow)
Qth may introduce a control dead-band which may not be desired. Set Qth to 0 for tight closed-loop
control and for maximum precision.
Select a Fixed Sensitivity
A fixed steering sensitivity is chosen if the valve shall output a flow which is only dependent on the
control error and Kp.
Sse Selects between a fixed steering sensitivity, variable to steering actuator position or vehicle speed.
Set Sse to 1 to select the fixed sensitivity
Sts0 Sets a gradient between steering angle and requested port flow. Sts0 is normally set when max port
flow (defined by Qm) is achieved at maximum steering device input.
The default value is a gradient matching maximum requested port flow to maximum port flow at the
maximum steering angle.
Symbol
Index
Default
Value range
Sse
5y09
1
Must be set at 1
Sts0
5y10
1000
0 to 1000 (amplification of 0 to 100 %)
Default Sts0 shall be changed to 1000.
Vehicle Speed Dependent Sensitivity
Variable steering sensitivity related to vehicle speed is normally used to optimize directional stability
automatically and beyond the notice of the driver. The values and correlation is normally close related to
the present vehicle dynamics of the individual vehicle model. The Sts value is used to amplify the input
signal as described in
The correlation is defined by seven parameters. All Sts-parameters may be set equal to each other or set
monotonically falling for increasing vehicle speeds. The steering sensitivity between two table
coordinates is found by linear interpolation. The relation is equal for negative speeds.
200
300
400
500
0
40
60
80
100
120
Sts0=105
Sts1=90
Sts2=75
Sts3=60
Sts4=45
Sts5=30
St
eer
ing sensitivit
y S
ts
(V
e)
Ve - Vehicle speed: 1 unit = 0.1 km/h
Vesm=500
Sts
(Ve)
saturates
max Sts = 1000
700
800
900
600
1000
min Sts = 20
100
Sse Selects between a fixed steering sensitivity, variable to steering actuator position or vehicle speed.
Set Sse to 3 to select the sensitivity related to vehicle speed.
Sts0 Sets the linear gradient between steering angle and requested port flow when the vehicle is
standing still. When the vehicle signal unintentionally not is mapped, Sts0 is applied constantly since
variable Ve remains 0.
In case the vehicle signal not is diagnosed, it is recommended to set Sts0 at a value where sufficient
directional stability at maximum vehicle speed is present.
Sts1 Sets the linear gradient between steering angle and requested port flow when the vehicle is driving
at 6.25% of the speed defined by parameter Vesm.
Operation Manual
PVED-CL Controller for Electro-Hydraulic Steering, Version 1.38
Auto-steering
96 |
©
Danfoss | May 2016
11025583 | AQ00000216en-US0302