DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
58
Danfoss Electronics spa
Air Handling seq.
- user manual
ALARMS TABLE
Code Description
Source
Type of
reset
Semi
automatic
period
(min)
Delay
at
start-
up
Operating
delay
Active
with
unit
OFF
Alarm
relay
Warning
relay
Buzzer Actuators
OFF
E07
Analog Input
7 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E08
Analog Input
8 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E09
Analog Input
9 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E10
Analog Input
10 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E11
Analog Input
11 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E12
Analog Input
12 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E13
Analog Input
13 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E14
Analog Input
14 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E15
Analog Input
15 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E16
Analog Input
16 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved\
Tab 40_ [Alarms - Alarms table]