4.5| Locking sequences
For each coil it is possible to lock the cooling or heating control if the outside temperature measured with the “OUT
– Outside Temp” probe goes beyond the following limits.
LOCKING SEQUENCES
COI
Coils
Min
Max
Default
U.M.
Text value
CL1
Coil 1
b29
Cooling lock
-40,0
100,0
-30,0
°C
b30
Heating lock
-40,0
100,0
90,0
°C
CL2
Coil 2
b59
Cooling lock
-40,0
100,0
-30,0
°C
b60
Heating lock
-40,0
100,0
90,0
°C
CL3
Coil 3
b89
Cooling lock
-40,0
100,0
-30,0
°C
b90
Heating lock
-40,0
100,0
90,0
°C
Tab 17_ [Coils control - Locking sequences]
Fig 11 _ [Coils control - Locking sequences]