DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
22
Danfoss Electronics spa
Air Handling seq.
- user manual
4.4.2|
Variable step switch
If b11, b41, b71 = VAR STEP, coil is step controlled in a variable way.
When variable step switch is selected, you have to set the number of steps (1..3) for each coil and for each step (of
each coil) the ON and OFF switching point in % of the load demand
VARIABILE STEP SWITCH
COI
Coils
Min
Max
Default
U.M.
Text value
CL1
Coil 1
b12
Number of steps
0
3
2
b17
Step 1 ON
0
1000
10,0
%
b18
Step 1 OFF
0
1000
20,0
%
b19
Step 2 ON
0
1000
40,0
%
b20
Step 2 OFF
0
1000
30,0
%
b21
Step 3 ON
0
1000
50,0
%
b22
Step 3 OFF
0
1000
100,0
%
CL2
Coil 2
b42
Number of steps
0
3
2
b47
Step 1 ON
0
1000
10,0
%
b48
Step 1 OFF
0
1000
0,0
%
b49
Step 2 ON
0
1000
10,0
%
b50
Step 2 OFF
0
1000
30,0
%
b51
Step 3 ON
0
1000
50,0
%
b52
Step 3 OFF
0
1000
33,0
%
CL3
Coil 3
b72
Number of steps
0
3
2
b77
Step 1 ON
0
1000
17,0
%
b78
Step 1 OFF
0
1000
0,0
%
b79
Step 2 ON
0
1000
33,0
%
b80
Step 2 OFF
0
1000
17,0
%
b81
Step 3 ON
0
1000
50,0
%
b82
Step 3 OFF
0
1000
33,0
%
Tab 15_ [Coils control - Variable step switch]