Danfoss Electronics spa
Air Handling
seq.- user manual
DKRCC.PS.RI.A1.02 / 520H4358 - Air Handling Seq. user manual - V 2.2
Produced by Danfoss Electronics spa Graphic Department, 10-2009
57
ALARMS TABLE
Code Description
Source
Type of
reset
Semi
automatic
period
(min)
Delay
at
start-
up
Operating
delay
Active
with
unit
OFF
Alarm
relay
Warning
relay
Buzzer Actuators
OFF
A03
Supply fan
safety switch
Digital input
“SupFan SafeSW”
-1
(automatic)
0
0
0
NO
YES
YES
YES
Supply fan
A04
Return fan
alarm
Digital input
“RetFan Alarm
-1
(automatic)
0
0
0
NO
YES
YES
YES
Return fan
A05
Mixing damper
locked
Digital input
“MixDamp
Closed” and
output “Mixing
Damper” active
-1
(automatic)
0
0
3
NO
YES
YES
YES
Return fan
A06
Return fan
safety switch
Digital input
“RetFan SafeSW
-1
(automatic)
0
0
0
NO
YES
YES
YES
Return fan
A07
Freeze alarm
Digital input
“Freeze Alarm”
or Analog input
(defined in FP1)
<= FP2
-1
(automatic)
0
0
0
NO
YES
YES
YES
See ”9 Frost
protection”
A08
Fire alarm
Digital input “Fire
Alarm”
0 (manual)
0
0
0
YES
YES
YES
YES
All
A09
Supply air flow
alarm
Digital input
“Supply Flow”
0 (manual)
0
10
5
NO
YES
YES
YES
Supply fan
A10
Return air flow
alarm
Digital input
“Return Flow”
0 (manual)
0
10
5
NO
YES
YES
YES
Return fan
A11
Supply filter
alarm
Digital input
“Supply Filter”
0 (manual)
0
10
5
NO
YES
YES
YES
None
A12
Return filter
alarm
Digital input
“Return Filter”
0 (manual)
0
10
5
NO
YES
YES
YES
None
A13
Pump 1
overload
Digital input
“Coil1 Pump”
-1
(automatic)
0
0
0
NO
YES
YES
YES
Pump 1
A14
Pump 2
overload
Digital input
“Coil2 Pump”
-1
(automatic)
0
0
0
NO
YES
YES
YES
Pump 2
A15
Pump 3
overload
Digital input
“Coil3 Pump”
-1
(automatic)
0
0
0
NO
YES
YES
YES
Pump 3
A16
Coil 1 alarm
Digital input
“Coil1 Alarm”
-1
(automatic)
0
0
0
NO
YES
YES
YES
Coil 1
A17
Coil 2 alarm
Digital input
“Coil2 Alarm”
-1
(automatic)
0
0
0
NO
YES
YES
YES
Coil 2
A18
Coil 3 alarm
Digital input
“Coil3 Alarm”
-1
(automatic)
0
0
0
NO
YES
YES
YES
Coil 3
A19
Humidifier
alarm
Digital input
“Humidifier
Alarm”
-1
(automatic)
0
0
0
NO
YES
YES
YES
Humidifier
and pump
A20
Recovery
alarm
Digital input
“RecoveryAlarm”
-1
(automatic)
0
0
0
NO
YES
YES
YES
Recovery
and pump
A21
Generic alarm
Digital input
“Generic Alarm”
-1
(automatic)
0
0
0
NO
YES
YES
YES
None
AEX
No connection
with EXC
Module
Communication
error with EXC
extension
-1
(automatic)
0
30
5
NO
YES
YES
NO
Actuators
involved
E01
Analog Input
1 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E02
Analog Input
2 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E03
Analog Input
3 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E04
Analog Input
4 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E05
Analog Input
5 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved
E06
Analog Input
6 fault
Probe open or
short circuited
-1
(automatic)
0
20
10
NO
YES
YES
NO
Actuators
involved