7.7 Parameter ID overview
A275.x or A375.x —
x
refers to the subtypes listed in the column.
ID
Parameter
Name
A275.x
A375.x
Setting
range
Factory
Unit
Own settings
11004
Desired T
4, 5
5 ... 150
50
°C
11010
ECA addr.
1, 2, 3
1, 2, 3, 4, 5
OFF ; A ; B
OFF
11011
Auto saving
1, 2, 3
1, 2, 3, 4, 5
OFF, -29 ... 10
-15
°C
11012
Boost
1, 2, 3
1, 2, 3, 4, 5
OFF, 1 ... 99
OFF
%
11014
Optimizer
1, 2, 3
1, 2, 3, 4, 5
OFF, 10 ... 59
OFF
11015
Adapt. time
1, 2, 3
1, 2, 3, 4, 5
OFF, 1 ... 50
OFF
Sec
11017
Demand
offset
1, 2, 3
1, 2, 3, 4, 5
OFF, 1 ... 20
OFF
K
11020
Based on
1, 2, 3
1, 2, 3, 4, 5
OUT ; ROOM
OUT
11021
Total stop
1, 2, 3
1, 2, 3, 4, 5
OFF ; ON
OFF
11022
P exercise
1, 2, 3
1, 2, 3, 4, 5
OFF ; ON
ON
11026
Pre-stop
1, 2, 3
1, 2, 3, 4, 5
OFF ; ON
ON
11028
Con. T, ret. T
lim.
4, 5
10 ... 110
70
°C
11029
DHW, ret. T
limit
4, 5
OFF, 10 ... 110
OFF
°C
11031
High T out X1
1, 2, 3
1, 2, 3, 4, 5
-60 ... 20
15
°C
11032
Low limit Y1
1, 2, 3
1, 2, 3, 4, 5
10 ... 150
35
°C
11033
Low T out X2
1, 2, 3
1, 2, 3, 4, 5
-60 ... 20
-15
°C
11034
High limit Y2
1, 2, 3
1, 2, 3, 4, 5
10 ... 150
35
°C
11035
Infl. - max.
1, 2, 3
1, 2, 3, 4, 5
-9.9 ... 9.9
0.0
11036
Infl. - min.
1, 2, 3
1, 2, 3, 4, 5
-9.9 ... 9.9
0.0
11037
Adapt. time
1, 2, 3
1, 2, 3, 4, 5
OFF, 1 ... 50
25
Sec
11038
Stop at T out
1, 2, 3
1, 2, 3
-49 ... 49, OFF
OFF
°C
11040
P post-run
1, 2, 3
1, 2, 3, 4, 5
0 ... 99
3
Min
11046
Difference
1, 2, 3
OFF, 1 ... 50
8
K
-||-
1, 2, 3, 4, 5
1 ... 50
8
K
11047
Protection
1, 2, 3
1, 2, 3
OFF ; ON
OFF
11048
Band limit
1, 2, 3
5 ... 80
20
K
11049
Max. T limit
1, 2, 3
1, 2, 3
40 ... 150
90
°C
11050
P demand
1, 2, 3
1, 2, 3, 4, 5
OFF ; ON
OFF
11071
Min. ON time
1, 2, 3
1, 2, 3
0 ... 9
0
Min
11072
Sequence
type
1, 2, 3
0 ... 5
3
11073
Steps
1, 2, 3
1 ... 8
1
11074
Reaction, o.
band
1, 2, 3
5 ... 6000
60
Sec
11075
Reaction, in
band
1, 2, 3
5 ... 6000
120
Sec
11077
P frost T
1, 2, 3
1, 2, 3, 4, 5
OFF, -10 ... 20
2
°C
VI.GU.L2.02
© Danfoss | 2017.09 | 193
Operating Guide ECL Comfort 210/296/310, application A275/A375