5.7 Boiler
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Boiler
Stop at T out
1x038
A275 applications:
If the outdoor temperature is higher than the set value, the burner will not
be cut-in.
A375 applications:
If the outdoor temperature is higher than the set value, the last burner step
will not be cut-in.
See Appendix “Parameter ID overview”
–49 ... 49:
Set the value for blocking the last burner step.
OFF:
The 'Stop at T out' function is not active.
The ‘Stop at T out’ can be used in connection with alternative heat
supply sources such as heat pumps and solar systems.
MENU > Settings > Boiler
Difference
1x046
The burner is switched ON and OFF to maintain the desired boiler
temperature. Set the difference between the cut-in and cut-out temperature.
See Appendix “Parameter ID overview”
OFF:
(Only in A275 applications):
The boiler temperature difference is set
automatically according to the momentary load of
the boiler and the temperature conditions in the
heating system.
1 ... 50 K:
The boiler temperature difference is set to a
fixed value according to the boiler manufacturer
specification.
Temp.
Actual boiler / flow
temp.
Difference
Desired boiler / flow
temp.
Time
The boiler temperature difference is symmetrical around the desired
boiler temperature, i.e. half the value is above and half the value is
below this temperature.
VI.GU.L2.02
© Danfoss | 2017.09 | 127
Operating Guide ECL Comfort 210/296/310, application A275/A375