MENU > Settings > Flow (boiler) temperature
Desired T (Desired flow temperature)
1x004
When the ECL Comfort is in override mode, type "Const. T", the desired flow
temperature can be set.
A "Const. T" related return temperature limitation can also be set. See MENU
> Settings > Return limit > 'Con. T, ret. T lim.'
See Appendix “Parameter ID overview”
Override mode
When ECL Comfort is in Scheduled mode, a contact (switch) signal can
be applied to an input in order to override to Comfort, Saving, Frost
Protection or Constant temperature. As long as the contact (switch)
signal is applied, the override is active.
The "Desired T" value can be influenced by:
•
temp. max.
•
temp. min.
•
room temp. limit
•
return temp. limit
•
flow / power limit
MENU > Settings > Flow (boiler) temperature
Temp. min.
1x177
See Appendix “Parameter ID overview”
Set the min. duct / flow / inlet temperature for the system. The
desired duct / flow / inlet temperature will not be lower than this
setting. Adjust the factory setting, if required.
‘Temp. min.’ is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
‘Temp. min.’ can be overruled by the influence from the return
temperature limitation (see 'Priority').
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
MENU > Settings > Flow (boiler) temperature
Temp. max.
1x178
See Appendix “Parameter ID overview”
Set the max. flow / duct / inlet temperature for the system. The
desired temperature will not be higher than this setting. Adjust
the factory setting, if required.
The setting of ‘heat curve’ is possible for heating circuits only.
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
VI.GU.L2.02
© Danfoss | 2017.09 | 107
Operating Guide ECL Comfort 210/296/310, application A275/A375