A375.1, example f
Up to 4 x boiler ON / OFF control for a heating circuit.
* = pressure relief valve
Rotating sequence of the boilers: Boiler 1 - 2 - 3 - 4. Next day: Boiler 2 - 3 - 4 -1. Following day: Boiler 3 - 4 -1 - 2 and so on.
Burner steps are activated according to heat demand.
The last burner step can be disabled if the outdoor temperaure is higher than a set value.
Special settings for type A375.1, example f:
Navigation:
ID no.:
Recommended setting:
Heating circuit (circuit 1)
Sequence type (code) for controlling the burners:
MENU \ Settings \ Boiler: 'Sequence type'
11072
0
Number of total burner steps:
MENU \ Settings \ Boiler: ‘Steps'
11073
4
VI.GU.L2.02
© Danfoss | 2017.09 | 37
Operating Guide ECL Comfort 210/296/310, application A275/A375