5.12 Anti-bacteria
On selected days during the week the DHW temperature can
be increased in order to neutralize bacteria in the DHW system.
The desired DHW temperature 'Desired T' (typically 80 °C) will be
present for the selected day(s) and duration.
The anti-bacteria function is not active in frost protection mode.
X
=
Time
Y
=
Desired DHW temperature
# 1 #
=
Duration
# 2 #
=
Desired Anti-bacteria temperature value
# 3 #
=
Desired Anti-bacteria temperature
# 4 #
=
Desired DHW temperature value
# 5 #
=
Start time
During the anti-bacteria process, the return temperature limitation is
not active.
MENU > Settings > Anti-bacteria
Day
Select (mark) the day(s) of the week where the anti-bacteria function must
be active.
M = Monday
T
= Tuesday
W = Wednesday
T
= Thursday
F
= Friday
S
= Saturday
S
= Sunday
154 | © Danfoss | 2017.09
VI.GU.L2.02
Operating Guide ECL Comfort 210/296/310, application A275/A375