A375 APPLICATIONS:
A375.1, example a
One boiler with 2 x burner ON / OFF control for a heating circuit.
* = pressure relief valve
Fixed sequence: Burner 1 must be switched ON before burner 2 can be switched ON.
Burner 1 is active at low heat demand. At increased heat demand burner 2 is activated additionally.
The last burner step can be disabled if the outdoor temperaure is higher than a set value.
Special settings for type A375.1, example a:
Navigation:
ID no.:
Recommended setting:
Heating circuit (circuit 1)
Sequence type (code) for controlling the burners:
MENU \ Settings \ Boiler: 'Sequence type'
11072
3
Number of total burner steps:
MENU \ Settings \ Boiler: ‘Steps'
11073
2
32 | © Danfoss | 2017.09
VI.GU.L2.02
Operating Guide ECL Comfort 210/296/310, application A275/A375