MENU > Settings > Optimization
Boost
1x012
Shortens the heating-up period by increasing the desired flow temperature
by the percentage you set.
See Appendix “Parameter ID overview”
OFF:
The boost function is not active.
Value:
The desired flow temperature is increased temporarily
with the set percentage.
In order to shorten the heating-up period after a saving
temperature period, the desired flow temperature can be increased
temporarily (max. 1 hour). At optimizing the boost is active in the
optimization period ('Optimizer').
If a room temperature sensor or an ECA 30 / 31 is connected, the
boost stops when the room temperature is reached.
MENU > Settings > Optimization
Ramp (reference ramping)
1x013
The time (minutes) in which the desired flow temperature increases
gradually to avoid load peaks in the heat supply.
See Appendix “Parameter ID overview”
OFF:
The ramping function is not active.
Value:
The desired flow temperature is increased gradually with
the set minutes.
In order to avoid load peaks in the supply network, the flow
temperature can be set to increase gradually after a period with
saving temperature. This causes the valve to open gradually.
X
= Time
Y
= Desired flow temperature
# 1#
= Ramping time
= Comfort temperature
= Saving temperature
VI.GU.L2.02
© Danfoss | 2017.09 | 123
Operating Guide ECL Comfort 210/296/310, application A275/A375