5.9 Application
The section "Application" describes specific application related
issues.
Some of the parameter descriptions are universal for different
application keys.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Application
ECA addr. (ECA address, choice of Remote Control Unit)
1x010
Decides the room temperature signal transfer and communication with the
Remote Control Unit.
See Appendix “Parameter ID overview”
OFF:
No Remote Control Unit. Only room temperature sensor,
if any.
A:
Remote Control Unit ECA 30 / 31 with address A.
B:
Remote Control Unit ECA 30 / 31 with address B.
The Remote Control Unit must be set accordingly (A or B).
MENU > Settings > Application
Demand offset
1x017
The desired flow temperature in heating circuit 1 can be influenced by the
demand for a desired flow temperature from another controller (slave) or
another circuit.
See Appendix “Parameter ID overview”
OFF:
The desired flow temperature in circuit 1 is not
influenced by the demand of any other controller (slave
or circuit 2).
Value:
The desired flow temperature is increased by the set
value in ‘Demand offset’, if the demand of the slave /
circuit 2 is higher.
Temp.
Setting in
‘Demand offset’
Des. flow temp.,
circuit 1
Des. flow temp.,
circuit 2
Time
The function of ‘Demand offset’ can compensate for heat losses
between master and slave controlled systems.
MENU > Settings > Application
P exercise (pump exercise)
1x022
Exercises the pump to avoid blocking in periods without heat demand.
See Appendix “Parameter ID overview”
OFF:
The pump exercise is not active.
ON:
The pump is switched ON for 1 minute every third day at
noon (12:14 hours).