User Guide
|
Controller for appliance control, AK-CC 450
RS8EU702 | 27
© Danfoss | ADAP-KOOL® | 2015.10
Case
Room
Defrost stop on
time
Defrost stop
on S5
Defrost stop on
time
Defrost stop
on S5
Preset settings (o62)
1
2
3
4
5
6
Temperature (SP)
2°C
-2°C
-28°C
4°C
0°C
-22°C
Max. temp. setting (r02)
6°C
4°C
-22°C
8°C
5°C
-20°C
Min. temp. setting (r03)
0°C
-4°C
-30°C
0°C
-2°C
-24°C
Sensor signal for thermostat. S4% (r15)
100%
0%
Alarm limit high (A13)
8°C
6°C
-15°C
10°C
8°C
-15°C
Alarm limit low (A14)
-5°C
-5°C
-30°C
0°C
0°C
-30°C
Sensor signal for alarm funct.S4% (A36)
0%
100%
0%
Interval between defrost (d03)
6 h
6h
12h
8h
8h
6h
Defrost sensor: 0=time, 1=S5, 2=S4 (d10)
0
1
1
0
1
1
DI1 config. (o02)
Case cleaning (=10)
Door function (=2)
Sensor signal for display view S4% (017)
0%
Note: For applications 6 and 7 the sensor weighting for the S3/S4 sensors is not used for the thermostat, alarm thermostat and display readings as the
sensor uses are predefined.
Auxiliary schedule for settings (quick-setup)