User Guide
|
Controller for appliance control, AK-CC 450
© Danfoss | ADAP-KOOL® | 2015.10
30 | RS8EU702 |
Network address (0= off)
o03
1
1
1
1
1
1
1
1
1
0
240
0
On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
(used at LON 485 only and DANBUSS)
o04
1
1
1
1
1
1
1
1
1
0/Off
1/On
0/Off
Access code 1 (all settings)
o05
1
1
1
1
1
1
1
1
1
0
100
0
Used sensor type
: 0=Pt1000, 1=Ptc1000,
o06
1
1
1
1
1
1
1
1
1
0/Pt
1/Ptc
0/Pt
Software Version
o08
1
1
1
1
1
1
1
1
1
100
999
Max hold time after coordinated defrost
o16
1
1
1
1
1
1
1
1
1
0 min.
360 min.
20
Select signal for display view. S4% (100%=S4, 0%=S3)
o17
1
1
1
1
1
0 %
100 %
100
Input signal on DI2. Function:
(0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start (pulse-
signal). 5=ext. main switch 6=night operation 7=
Thermostat
band changeover
(activate r21). 8=alarm function when
closed. 9=alarm function when open. 10=case cleaning (pulse
signal). 11=forced cooling at hot gas defrost.). 12=night cover,
13=coordinated defrost). 15=application shutdown
o37
1
1
1
1
1
1
1
1
1
0
15
0
Configuration of light function
: 1=Light follows day /night
operation, 2=Light control via data communication via
‘o39’, 3=Light control with a DI-input, 4=As "2", but light
switch on and night cover will open if the network cut out
for more than 15 minutes.
o38
1
1
1
1
1
1
1
1
1
1
4
1
Activation of light relay (only if o38=2)
On=light
o39
1
1
1
1
1
1
1
1
1
0/Off
1/On
0/Off
Rail heat On time during day operations
o41
1
1
1
1
0 %
100 %
100
Rail heat On time during night operations
o42
1
1
1
1
0 %
100 %
100
Rail heat period time (On time + Off time)
o43
1
1
1
1
6 min.
60 min.
10
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output
Off.
***
o46
1
1
1
1
1
1
1
1
1
0
2
0
Selection of EL diagram. See overview page 12 and 13
*
o61
1
1
1
1
1
1
1
1
1
1
8
1
Download a set of predetermined settings. See overview page
27
*
o62
1
1
1
1
1
1
1
1
1
0
6
0
Access code 2 (partial access)
***
o64
1
1
1
1
1
1
1
1
1
0
100
0
Replace the controllers factory settings with the present set-
tings
o67
1
1
1
1
1
1
1
1
1
0/Off
1/On
0/Off
Input signal on DI3. Function:
(0=not used. 1=status on DI2. 2=door function with alarm
when open. 3=door alarm when open. 4=defrost start (pulse-
signal). 5=ext. main switch 6=night operation,
7=Thermostat
band changeover
(activate
r21). 8=Not used. 9=Not used.
10=case cleaning (pulse signal). 11=forced cooling at hot gas
defrost,
12=night cover. 13=Not used. 14=Refrigeration
stopped (forced closing)). 15= application shutdown
o84
1
1
1
1
1
1
1
1
1
0
15
0
Rail heat control
0=not used, 1=pulse control with timer function (o41 and
o42), 2=pulse control with dew point function
o85
1
1
1
1
0
2
0
Dew point value where the rail heat is minimum
o86
1
1
1
1
-10°C
50°C
8
Dew point value where the rail heat is 100% on
o87
1
1
1
1
-9°C
50°C
17
Lowest permitted rail heat effect in %
o88
1
1
1
1
0 %
100 %
30
Time delay from "open door” refrigeration is started
o89
1
1
1
1
1
1
1
1
1
0 min.
240 min.
30
Fan operation on stopped refrigeration (forced closing):
0 = Stopped (defrosting permitted)
1= Running (defrosting permitted)
2=Stopped (defrosting not permitted)
3= Running (defrosting not permitted)
o90
1
1
1
1
1
1
1
1
1
0
3
1
Definition of readings on lower button:
1=defrost stop temperature, 2=S6 temperature, 3=S5_B
temperature. 4= Readout of S3B temperature
o92
1
1
1
1
1
1
1
1
1
1
4
1
Display of temperature
1= u56 Air temperature
2= u36 product temperature
o97
1
1
1
1
1
1
1
1
1
1
2
1
Light and night blinds defined
0: Light is switch off and night blind is open when the
main switch is off
1: Light and night blind is independent of main switch
o98
1
1
1
1
1
1
1
1
1
0
1
0
Continued
Code
1 2 3
4
5 6 7
8
9
Min.
Max.
Fac.
Actual