 Controller for appliance control, AK-CC 450

© Danfoss | ADAP-KOOL® | 2015.10  

28 | RS8EU702 | 

Menu survey

SW = 1.8x

Parameter

EL-diagram page 12 or 13

Min.-

value

Max.-value Factory 

setting

Actual 

setting

Function

Code

 1

2

 3

4

5

6

7

8

9

Normal operation
Temperature (setpoint)       

- - -

1

1

1

1

1

1

1

1

1

-50°C

50°C

2

Thermostat
Differential

r01

1

1

1

1

1

1

1

1

1

0.1 K

20 K

2

Max. limitation of setpoint setting

r02 

1

1

1

1

1

1

1

1

1

-49°C

50°C

50

Min. limitation of setpoint setting

r03 

1

1

1

1

1

1

1

1

1

-50°C

49°C

-50

Adjustment of temperature indication

r04

1

1

1

1

1

1

1

1

1

-10

10

0

Temperature unit (°C/°F)

r05 

1

1

1

1

1

1

1

1

1

0/°C

1/F

0/°C

Correction of the signal from S4

r09 

1

1

1

1

1

1

1

1

1

-10 K

10 K

0

Correction of the signal from S3

r10 

1

1

1

1

1

1

1

1

1

-10 K

10 K

0

Manual service, stop regulation, start regulation (-1, 0, 1)

r12 

1

1

1

1

1

1

1

1

1

-1

1

0

Displacement of reference during night operation

r13

1

1

1

1

1

1

1

1

1

-50 K

50 K

0

Define thermostat function
1=ON/OFF, 2=Pulse width modulating (PWM)

r14

1

1

1

1

1

1

1

1

1

1

2

1

Definition and weighting, if applicable, of thermostat sensors - 

S4% (100%=S4,  0%=S3)

r15

1

1

1

1

1

1

0 %

100 %

100

Time between melt periods

r16 

1

1

1

1

1

1

1

1

1

0 hrs

10 hrs

1

Duration of melt periods

r17

1

1

1

1

1

1

1

1

1

0 min.

30 min.

5

Temperature setting for thermostat band 2 

. As differential use 

r01 for application 1-8. r93 for application 9

r21

1

1

1

1

1

1

1

1

1

-50°C

50°C

2

Correction of the signal from 

S3B

r53

1

1

1

-10 K

10 K

0

Correction of the signal from 

S6

r59

1

1

1

1

1

1

1

1

1

-10 K

10 K

0

Correction of the signal from 

S6B

r60

1

-10 K

10 K

0

Definition and weighting, if applicable, of thermostat sensors 

 

when night cover is on.  (100%=S4,  0%=S3)

r61

1

1

1

1

1

1

0 %

100 %

100

Heat function

Neutral zone between refrigeration and heat function

r62

1

0 K

50 K

2

Time delay at switch between refrigeration and heat 

function 

r63

1

1

0 min.

240 min.

0

Differential for thermostat band 2

r93

1

0.1

20 K

2 K

Alarms

Delay for temperature alarm

A03

1

1

1

1

1

1

1

1

1

0 min.

240 min.

30

Delay for door alarm

A04

1

1

1

1

1

1

1

1

1

0 min.

240 min.

60

Delay for temperature alarm after defrost

A12

1

1

1

1

1

1

1

1

1

0 min.

240 min.

90

High alarm limit for thermostat 1

A13

1

1

1

1

1

1

1

1

1

-50°C

50°C

8

Low alarm limit for thermostat 1

A14 

1

1

1

1

1

1

1

1

1

-50°C

50°C

-30

High alarm limit for thermostat 2

A20

1

1

1

1

1

1

1

1

1

-50°C

50°C

8

Low alarm limit for thermostat 2

A21

1

1

1

1

1

1

1

1

1

-50°C

50°C

-30

High alarm limit for sensor S6 at thermostat 1

A22

1

1

1

1

1

1

1

1

1

-50°C

50°C

8

Low alarm limit for sensor S6 at thermostat 1

A23

1

1

1

1

1

1

1

1

1

-50°C

50°C

-30

High alarm limit for sensor S6 at thermostat 2

A24

1

1

1

1

1

1

1

1

1

-50°C

50°C

8

Low alarm limit for sensor S6 at thermostat 2

A25

1

1

1

1

1

1

1

1

1

-50°C

50°C

-30

S6 alarm time delay
With setting = 240 the S6 alarm will be omitted

A26

1

1

1

1

1

1

1

1

1

0 min.

240 min.

240

Alarm time delay or signal on the DI1 input

A27

1

1

1

1

1

1

1

1

1

0 min.

240 min.

30

Alarm time delay or signal on the DI2 input

A28

1

1

1

1

1

1

1

1

1

0 min.

240 min.

30

Signal for alarm thermostat. S4% (100%=S4, 0%=S3)

A36

1

1

1

1

1

1

0 %

100 %

100

Delay for S6 (product sensor alarm) after defrost

A52

1

1

1

1

1

1

1

1

1

0 min.

240 min.

90

Delay for S3B alarm during normal regulation

A53

1

1

0 min.

240 min.

90

Compressor
Min. ON-time

c01

1

1

1

1

1

1

1

1

1

0 min.

30 min.

0

Min. OFF-time

c02

1

1

1

1

1

1

1

1

1

0 min.

30 min.

0

Time delay for cutin of comp.2

c05

1

1

0 sec

999 sec

5

Step Mode 1= Sequential, 2=Cyclic

c08

1

1

2

2

Comp.2 can run in thermostat band 2

0: No

1: Yes

c85

1

0

1

0

Comp. on time when sensor fault

c86

1

0 min

240 min

15

Содержание AK-CC 450

Страница 1: ...Controller for appliance control AK CC 450 User Guide...

Страница 2: ...appliance The temperature of the evaporator is registered with the S5 sensor which can be used as a defrosting sensor In addition to the output for the solenoid valve the controller has 5 relay output...

Страница 3: ...o refrigeration sections There are two defrost sensors one for each evaporator Application 6 Here the temperature and alarm monitoring are always controlled using the S4 sensor The two S3 temperatures...

Страница 4: ...it can only be used in DX central plant or brine system In principle regulation in this system is the same as described above but is now performed with a PI function This results in reduced fluctuati...

Страница 5: ...the appliance can also be used and which can register and monitor the temperature in the warmest part of the appliance There are separate alarm limits and time delays for the product sensor Appliance...

Страница 6: ...he PMLX GPLX valve is closed completely before the hotgas is turned on Drip tray heating element It is possible to control a heating element in the drip tray for hot gas defrosting When defrosting is...

Страница 7: ...a message to the system unit and then goes into a waiting position When every controller in the group is in a waiting position refrigeration is again permitted in all the individual controllers Defros...

Страница 8: ...eration Here compressor 1 will start as the first one and when needed compressor 2 will be started Determined by thermostat band The compressor operating mode can be set in application 9 so that both...

Страница 9: ...communication from a system unit Here there are two operational options if data communication should fail The light can go ON The light can stay in its current mode The light load must be connected t...

Страница 10: ...defined for two different applications Alarm monitoring The controller monitors the door contact and delivers an alarm message if the door has been opened for a longer period than the set alarm delay...

Страница 11: ...connected to the built in MODBUS the display can advantageously be changed to a type with screw terminals I e the type EKA 163A or EKA 164A If connection of two displays is required one must be conne...

Страница 12: ...ration appliances or cold storage rooms In general all have outputs for Solenoid valve or compressor Fan Defrost Light In addition they have different uses and thereby input and outputs Application 1...

Страница 13: ...nd two refrigeration sections The temperature is always controlled according to the S4 temperature There are two S3 sensors Alarm monitoring and display readings take place individually via the S3 sen...

Страница 14: ...tory indicating application 1 If you employ another use labels are provided so that you can mount the relevant one For application 2 to 5 and 9 it is only the lower label that needs to be mounted For...

Страница 15: ...in C or in F r05 Temp unit C 0 F 1 Only C on AKM whatever the setting Correction of signal from S4 Compensation possibility due to long sensor cable r09 Adjust S4 Correction of signal from S3 Compensa...

Страница 16: ...des LED will flash on the controller front panel and the alarm relay will cut in With data communication the impor tance of the individual alarms can be defined Setting is carried out in the Alarm des...

Страница 17: ...hen defrosts start Min ON time in minutes c01 Min On time Min OFF time in minutes c02 Min Off time Time delay for couplings of two compressors Settings indicate the time that has to elapse from the fi...

Страница 18: ...only relevant if you have chosen defrost with interval start d03 The function delays the interval time d03 by the set number of minutes but it only does it once and this at the very first defrost tak...

Страница 19: ...Tn sec Fan Fan control Fan stop temperature The function stops the fans in an error situation so that they will not provide power to the appliance If the defrost sensor registers a higher temperature...

Страница 20: ...input is closed 12 Night blinds Pulse signal activates the night blinds 13 14 Not used 15 Case Shutdown when input is closed o02 DI 1 Config Definition takes place with the numerical value shown to t...

Страница 21: ...en the door is closed again there will be a time delay of two minutes before the light is switched off 4 As 2 but if there are any 15 minute network errors the light will switch on and the night blind...

Страница 22: ...on This function requires that a signal is received about the dew point value The value is measured by a system manager and sent to the controller via the data communication o85 Railh mode Dew point v...

Страница 23: ...mperature Weighted S3 S4 u56 Display air Measured temperature for alarm thermostat u57 Alarm air Status on relay for cooling u58 Comp1 LLSV Status on relay for fan u59 Fan relay Status on relay for de...

Страница 24: ...s operating it must run for at least x minutes S2 2 When the compressor is stopped it must remain stopped for at least x minutes S3 3 The evaporator drips off and waits for the time to run out S4 4 Re...

Страница 25: ...frost 16 A13 High temp S6 Temperature alarm High S6 1 A14 Low temp S6 Temperature alarm Low S6 2 A15 DI1 alarm DI1 alarm 8 A16 DI2 alarm DI2 alarm 8 A45 Standby mode Standby position stopped refrigera...

Страница 26: ...found in a rolling stack Push the uppermost or lowermost button to scan the rolling stack Set temperature 1 Push the middle button until the temperature value is shown 2 Push the upper or the lower bu...

Страница 27: ...thermostat S4 r15 100 0 Alarm limit high A13 8 C 6 C 15 C 10 C 8 C 15 C Alarm limit low A14 5 C 5 C 30 C 0 C 0 C 30 C Sensor signal for alarm funct S4 A36 0 100 0 Interval between defrost d03 6 h 6h 1...

Страница 28: ...1 0 100 100 Heat function Neutral zone between refrigeration and heat function r62 1 0 K 50 K 2 Time delay at switch between refrigeration and heat function r63 1 1 0 min 240 min 0 Differential for th...

Страница 29: ...at PWM n63 1 1 1 1 1 1 1 1 1 30 sec 900 sec 300 Max opening degree at PWM n64 1 1 1 1 1 1 1 1 1 0 100 100 Min opening degree at PWM n65 1 1 1 1 1 1 1 1 1 0 90 0 Expert setting Windup at PWM n66 1 1 1...

Страница 30: ...election of EL diagram See overview page 12 and 13 o61 1 1 1 1 1 1 1 1 1 1 8 1 Download a set of predetermined settings See overview page 27 o62 1 1 1 1 1 1 1 1 1 0 6 0 Access code 2 partial access o6...

Страница 31: ...u18 1 1 1 1 1 1 1 1 1 Temperature measured with S6 sensor product temperature u36 1 1 1 1 1 1 1 1 1 Status on DI2 output on 1 closed u37 1 1 1 1 1 1 1 1 1 Air temperature Weighted S3 S4 u56 1 1 1 1 1...

Страница 32: ...gateway must be version 6 20 or higher RJ45 For data communication but only if a TCP IP module is inserted in the controller OEM MODBUS For data communication Terminal 56 screen Terminal 57 A Terminal...

Страница 33: ...ight must be on DI3 Digital input signal The signal must have a voltage of 0 230 V AC The function is defined in o84 Data communication If data communication is used it is important that the installat...

Страница 34: ...Leak 1 mA Max 1 pcs coil Relays CE 250 V a c DO3 DO4 4 3 A DO2 DO5 DO6 4 3 A Environments 0 to 55 C During operations 40 to 70 C During transport 20 80 Rh not condensed No shock influence vibrations...

Страница 35: ...B8591 EKA 163B External display with plug for direct connection 084B8574 EKA 164B External display with operation buttons and plug for direct connections 084B8575 EKA 163A External display with screw...

Страница 36: ...This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this materi...

Отзывы: