Run test/ Cancel test:
Allows a duration test to be run or cancelled at that time. This
option will only appear if the necessary conditions are met (no power failure, battery
charged, no output circuit fault...).
If you want the test to run:
-
Automatically: set it to
Automatic: Yes
. You must also set the
Period
,
Test time
(shared with the functional test) and
Day of the week
.
-
Manually: set it to
Automatic: No
. Duration tests can be requested manually from the
display using the
Programme test
or
Run test options.
8.2.2.3. Capacity test
Overview
OK
Main menu
>
Test
OK
Mode
>
Dur
>
CAPACITY TEST
Last test:
07/05/16
4.6Ah
*I test:
30.2 A
#Run test
Func
Dur
Cap
Last test:
Indicates the date (mm/dd/yy) and result of the last capacity test performed.
I test:
Indicates the simulated consumption with which the capacity test is performed.
Cancel/Launch test:
It enables a capacity test to be ordered or cancelled if it is
running. One option or another or none is displayed depending on the status of the
device
To order the capacity test, simply configure the current to the desired battery discharge
rate and from there
“Run
test”.
The duration test can be configured to run automatically at a specific
time and day of the week in order to mitigate the risk of battery
discharge.
If the duration test period transpires without the device having
performed the test, the corresponding alarm is generated to alert the
user.
Although it is configured to run tests automatically, a manual test can
be performed as long as the necessary conditions are met.
!
Note that during execution of a duration te
st, the system’s
battery is fully discharged, so installation will not have the
required duration until at least 24 hours after completion of the
test.