www.daisalux.com
29
LPS24
– USER MANUAL
•
Not communicated:
this setting must be used if conventional luminaires are connected
to the circuit’s output. It provides voltage at its output during tests,
auxiliary switch
on or power failure. It also enables voltage to be provided in the absence of power.
•
Beacons:
this setting must be used if beacons are connected to the circuit’s output. It
provides voltage at its output during tests, auxiliary switch on or power failure. It also
enables voltage to be provided in the absence of power. There are several dimming
configurations on the output.
I warn:
Overload alert limit. If the current demanded by the load circuit exceeds this
value, a fault will be generated in the circuit.
I measured:
Instantaneous measurement of the circuit’s current
Mode:
configure the circuit’s behaviour in the presence of power supply.
For circuits of
the
type “ELC” the configuration is performed on all luminaires of the circuit.
•
Maintained:
when power is present, voltage is supplied to the load connected to its
output.
•
Non maintained:
when power is present, voltage is not supplied to the load connected
to its output.
Delay to alert:
set a time delay for the entire circuit on the return to alert. Not available
for “
ELC
” type circuits because in such circuits configuration should be made at the
luminaire level.
P. lum fail:
only available for “
Non-communicated type
” circuits. Deactivate or
configure
a threshold in watts (w) to generate an alarm if consumption is above or below the
threshold once calibrated.
Recalibrate:
only available for “
Non-communicated type
” circuits. Calibrate the
consumption of the circuit to obtain the reference value.
DBR:
Only available for “
beacons type
” circuits. Configures whether the circuit attends to
the activation of the DBR signal. If it attends to the signal, when it is active it performs a
variable switch on from the DBR min dimming value to the DBR max dimming value.
External dimming:
only available for “
beacons type
” circuits. Configures whether the
circuit serves the analogue input (0-10 v) to dim the circuit when connected to power.
Alert dimming:
percentage of dimming in the presence of mains. Only available for
“
beacons type
” circuits.
Emerg dimming:
percentage of dimming in the absence of mains. Only available for
“
beacons type
” circuits.
DBR min dimming:
minimum percentage of dimming during DBR activation. Only
available for “
beacons type
” circuits.
DBR max dimming:
maximum percentage of dimming during DBR activation. Only
available for “
beacons type
” circuits.
•
It is only an initial configuration, if after by another means (time
switch, an auxiliary input configuration) circuit switch on or switch off
is ordered, the new order will take precedence.
•
Configuring an auxiliary input with the “
on/off
” behaviour takes
precedence over this configuration.