SiAF332111E
Field Settings for Outdoor Unit (6/8 HP Models)
Part 5 Field Settings and Test Operation
133
3.6.2 Overview of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
Item
Contents
Description
Display
Description
Display
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
2
Low noise/
demand address
Used to make address setting for low
noise/demand address.
2.
0
2
Address:
0
~
31
3
0
1
5
Indoor fan
forced H
Used to force the fan of indoor unit to H
tap.
2.
0
5
Normal operation
Indoor fan H
0
1
6
Forced
thermostat ON
Used to force all indoor units to operate
forced thermostat ON.
2.
0
6
Normal operation
Forced thermostat ON
0
1
8
Te setting
Used to make setting of targeted
evaporating temperature for cooling
operation.
2.
0
8
Standard: 6°C
High sensible: 7°C
High sensible: 8°C
High sensible: 9°C
High sensible: 10°C
High sensible: 11°C
2
3
4
5
6
7
11
Eco setting is available from an external input.
When this configuration is set, it is not possible to turn the
Eco refrigerant control ON/OFF using the remote
controller. Also, depending on the settings, low noise
operation or demand operation may not be performed
using the external control adaptor.
2.
1
1
Unavailable
Demand input
Low noise level input
0
1
2
12
External low
noise/demand
setting
Used to receive external low noise or
demand signal.
2.
1
2
Input LNO/DE
OFF
ON
0
1
13
AIRNET
address
Used to set address of AIRNET
2.
1
3
Address:
0
~
63
6
0
3
18
High EST mode
for outdoor fan
High external static pressure mode
setting
2.
1
8
ON (Auto adjust and
re-judge)
OFF (Auto adjust without
re-judge)
Forced level 0
Forced level 1
Forced level 2
0
1
2
3
4
21
Refrigerant
recovery/
vacuuming
Used to set the system to refrigerant
recovery mode (without compressor
run).
2.
2
1
Refrigerant recovery
OFF
ON
0
1
22
Automatic
night-time low
noise operation
Automatic night-time low noise
operation. Time for the operation is
subject to the start and end time
settings.
2.
2
2
OFF
Level 1
Level 2
Level 3
0
1
2
3
23
Used to set Eco mode invalid.
When this configuration is set, it is not possible to turn the
Eco mode ON/OFF using the external control adaptor.
2.
2
3
Valid
Invalid for cooling
Invalid for heating
Invalid
0
1
2
3
25
External
night-time low
noise operation
level
Low noise level when the external low
noise signal is input at option
DTA104A61.
2.
2
5
Level 1
Level 2
Level 3
1
2
3
26
Automatic
night-time low
noise operation
start
Time to start automatic “night-time low
noise” operation. (“Night-time low noise”
level setting should also be made.)
2.
2
6
About 8:00 PM
About 10:00 PM
About 12:00 AM
1
2
3
27
Automatic
night-time low
noise operation
stop
Time to stop automatic “night-time low
noise” operation. (“Night-time low noise”
level setting should also be made.)
2.
2
7
About 6:00 AM
About 7:00 AM
About 8:00 AM
1
2
3
28
Power transistor
check
Used to troubleshoot DC compressor.
Inverter waveforms are output without
wire connections to the compressor. It is
useful to determine whether the relevant
trouble has resulted from the
compressor or inverter PCB.
2.
2
8
OFF
ON (10 Hz)
0
1
29
Capacity priority Cancel the low noise level control if
capacity is required while low noise
operation or night-time low noise
operation is in progress.
2.
2
9
OFF
ON
0
1
Содержание VRV S RXQ4/5ARV1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...