Control for 4/5/10/12 HP Outdoor Unit
Part 4 Functions and Control
65
1.4.4 Inverter Protection Control
Inverter current protection control and inverter fin temperature control are performed to prevent
tripping due to abnormality, transient inverter overcurrent, and fin temperature increase.
Inverter overcurrent protection control
Model
A
(A)
B
(A)
4HP
13.7
14.8
5HP
23.0
24.1
10/12HP
22.0
22.0
Not limited
Limited
Inverter current >
A
(A)
Inverter current >
A
(A)
Inverter current
≥
B
(A) × 10% continues for 260 seconds
•
Inverter current
≤
A
(A)
•
Compressor upper limit: Maximum frequency
&
•
10 seconds
•
Matching of frequency
&
Compressor upper limit
frequency: 1-step down from
current compressor frequency
Compressor upper limit
frequency: 1-step up from
current compressor frequency
Inverter current
standby
Inverter current
≤
A
(A)
continues for 3 minutes
Current step maintained
Without conditions
When occurring 4 times
within 60 minutes,
the error code
L8
is output.
Содержание VRV S RXQ4/5ARV1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...