Check
SiAF332111E
344
Part 6 Service Diagnosis
Note(s)
Reference
6.5 Wet Operation Check
CHECK 5
Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points.
1: Superheating temperature control in cooling is conducted by indoor unit electronic
expansion valve.
2: Guideline of superheating degree to judge as wet operation
(1) Suction gas superheating degree: Less than 3°C;
(2) Discharge gas superheating degree: Less than 15°C,
except immediately after compressor starts up or is running under dropping control.
(Use the above values as a guide. Depending on the other conditions, the unit may be normal
despite the values within the above range.)
CHECK 6
Refer to page 345.
Refrigerant stagnation
Overcharge of refrigerant
Defective crankcase heater
Frequent ON/OFF of compressor
[In cooling]
Indoor unit
electronic
expansion
valve opens too
much. (
∗
1)
Defective control
of superheating
degree
Defective
indoor unit
electronic
expansion
valve
Defective
control
Defective valve coil
Defective main PCB
Defective valve body
←
Refer to
CHECK 6
.
←
Are the coil resistance and
insulation normal?
←
Is the connector properly connected?
Are the thermistor resistance
characteristics normal?
←
Is the connector properly connected?
Are the thermistor resistance
characteristics normal?
←
Can the fan motor be rotated
with hands?
Are the motor coil resistance and
insulation normal?
←
Is the air filter clogged?
←
Is there any obstacle in the
airflow passage?
Wet operation
Degraded
evaporating
capacity
High
airflow
passage
resistance
Dirty evaporator
Decreased
airflow rate
Decreased
fan output
Defective fan motor
Dirty filter
Obstacles
←
Does the heat exchanger get clogged?
Defective main PCB
(including capacity
setting)
Defective gas pipe
thermistor of indoor unit
Defective liquid pipe
thermistor of indoor unit
Содержание VRV S RXQ4/5ARV1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...