Test Operation (4/5/10/12 HP Models)
SiAF332111E
168
Part 5 Field Settings and Test Operation
(4) Press the fan direction and strength buttons of the indoor unit to see if they operate properly.
About normal operation check
The compressor will not restart in about 5 minutes even if the ON/OFF button of the remote
controller is pressed.
When system operation is stopped by the remote controller, the outdoor unit may continue
operating for further 1 minute at maximum.
If any check operation was not performed through test operation on first installation, the error
code
U3
will be displayed. In this case, perform check operation in accordance with
Powering on to test operation
on page 166.
5.4.1 Error Codes and Corresponding Measures
Please check the remote controller connected to the indoor unit for verification.
Error code
Description
Solution
Primary
code
Sub code
E3
01
High pressure switch activated (S1PH)
Check the stop valve or (field) piping abnormality or
the airflow on the air cooling heat exchanger.
02
• Too much refrigerant charged
• Stop valve closed
• Check the amount of refrigerant and recharge the
unit.
• Open the stop valve.
13
Liquid stop valve closed.
Open the liquid stop valve.
18
• Too much refrigerant charged
• Stop valve closed
• Check the amount of refrigerant and recharge the
unit.
• Open the stop valve.
E4
01
Defective low pressure:
• Stop valve closed
• Refrigerant undercharged
• Defective indoor unit
• Open the stop valve.
• Check the amount of refrigerant and recharge the
unit.
• Check the user interface display.
• Check the transmission wiring between the indoor
and outdoor units.
E9
01
Defective electronic expansion valve (Subcooling)
(Y2E)
Check the connection of the PCB or the actuator.
04
Defective electronic expansion valve (Main) (Y1E)
Check the connection of the PCB or the actuator.
F3
01
Discharge pipe temperature too high (R21T):
• Stop valve closed
• Refrigerant undercharged
• Open the stop valve.
• Check the amount of refrigerant and recharge the
unit.
20
Compressor body temperature too high (R8T):
• Stop valve closed
• Refrigerant undercharged
• Open the stop valve.
• Check the amount of refrigerant and recharge the
unit.
F6
02
• Too much refrigerant charged
• Stop valve closed
• Open the stop valve.
• Check the amount of refrigerant and recharge the
unit.
H9
01
Defective outdoor air thermistor (R1T)
Check the connection of the PCB or the actuator.
J3
16
Defective discharge pipe thermistor (R21T):
Open circuit
Check the connection of the PCB or the actuator.
17
Defective discharge pipe thermistor (R21T):
Short circuit
Check the connection of the PCB or the actuator.
47
Defective compressor body thermistor (R8T):
Open circuit
Check the connection of the PCB or the actuator.
48
Defective compressor body thermistor (R8T):
Short circuit
Check the connection of the PCB or the actuator.
J5
01
Defective accumulator thermistor (R3T)
Check the connection of the PCB or the actuator.
J6
01
Defective heat exchanger deicer thermistor (R7T)
Check the connection of the PCB or the actuator.
J7
06
Defective subcooling heat exchanger liquid pipe
thermistor (R5T)
Check the connection of the PCB or the actuator.
J8
01
Defective heat exchanger liquid pipe thermistor (R4T) Check the connection of the PCB or the actuator.
J9
01
Defective subcooling heat exchanger gas pipe
thermistor (R6T)
Check the connection of the PCB or the actuator.
JA
06
Defective high pressure sensor (S1NPH): Open
circuit
Check the connection of the PCB or the actuator.
07
Defective high pressure sensor (S1NPH): Short
circuit
Check the connection of the PCB or the actuator.
JC
06
Defective low pressure sensor (S1NPL): Open circuit Check the connection of the PCB or the actuator.
07
Defective low pressure sensor (S1NPL): Short circuit Check the connection of the PCB or the actuator.
Содержание VRV S RXQ4/5ARV1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...