SiAF332111E
Control for 6/8 HP Outdoor Unit
Part 4 Functions and Control
79
2.7 Special Control
2.7.1 Pump Down Residual Control
Pc : High pressure sensor detection value
Pe : Low pressure sensor detection value
To avoid refrigerant emigration when outdoor unit stops operation (thermostat or safety), all
electronic expansion valves are closed.
2.7.2 Oil Return Control
In order to prevent the compressor from running out of oil, the oil return control is conducted to
recover oil that has flowed out from the compressor to the system side.
Tc : High pressure equivalent saturation temperature
Te : Low pressure equivalent saturation temperature
Ts1: Suction pipe temperature detected by thermistor R3T
Starting
Conditions
Oil return control is not conducted before 2 hours have elapsed from the activation of power
supply.
After 2 hours have elapsed, oil return control starts when the following item meets the
reference value.
• Total amount of oil discharged from the compressor
(The total amount of oil discharged from the compressor is computed from Tc, Te, and
compressor loads.)
Oil return control starts every 8 hours of cumulative operation of the compressor, even if the
reference value is not met.
Oil Return Control in Cooling Operation
Part Name
Electric
Symbol
RXMQ-AR
Function
Compressor motor
M1C
Capacity step PI control
Fan motor
M1F
TC control
Electronic expansion valve (Injection)
Y2E
0 pulse
Electronic expansion valve
(Refrigerant auto charge)
Y4E
480 pulse
Ending conditions
&
OR
· A lapse of 3 minutes.
· Ts1–Te < 3°C
· A lapse of 6 minutes
while the frequency
is more than that of
oil return control.
Indoor unit actuator
Cooling oil return control
Fan
Thermostat ON unit
Remote controller setting
Non-operating unit
OFF
Thermostat OFF unit
Remote controller setting
Electronic expansion valve
Thermostat ON unit
Normal control
Non-operating unit
224 pulse
Thermostat OFF unit
Normal control with forced thermostat
ON
Содержание VRV S RXQ4/5ARV1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...