SiAF332111E
Refrigerant Circuit (Piping Diagrams)
Part 2 Refrigerant Circuit
23
1.1.4 RXMQ10/12ARY1
No. in
piping
diagram
Electric
symbol
Name
Function
(1)
M1C
Compressor motor
Compressor is operated on frequencies between 60 Hz and 387.3 Hz by
using the inverter.
(2)
M1F
M2F
Fan motor
Since the system is of air heat exchanging type, the fan is operated at 8-step
rotation speed by using the inverter.
(3)
Y1E
Electronic expansion valve
(Main)
Fully open during cooling operation.
(4)
Y2E
Electronic expansion valve
(Injection)
Used to cool the compressor by injecting refrigerant when the compressor
discharge pipe temperature is high.
(5)
Y2S
Solenoid valve
(Accumulator oil return)
Used to return oil from the accumulator to the compressor.
(6)
S1NPH
High pressure sensor
Used to detect high pressure.
(7)
S1NPL
Low pressure sensor
Used to detect low pressure.
(8)
S1PH
High pressure switch
In order to prevent the increase of high pressure when an error occurs, this
switch is activated at high pressure of 4.0 MPa or more to stop the
compressor operation.
(9)
—
Pressure regulating valve
(Receiver to discharge pipe)
This valve opens at a pressure of 4.0 MPa to prevent pressure increase, thus
protecting functional parts from damage due to the increase of pressure in
transportation or storage.
(10)
—
Capillary tube
Used to return the refrigerating oil separated through the oil separator to the
compressor.
(11)
R1T
Thermistor (Outdoor air)
Used to detect outdoor air temperature, correct discharge pipe temperature,
and for other purposes.
(12)
R21T
Thermistor (Discharge pipe)
Used to detect discharge pipe temperature, for temperature protection control
of the compressor, and for other purposes.
(13)
R3T
Thermistor (Accumulator)
Used to detect gas pipe temperature at the accumulator inlet.
(14)
R4T
Thermistor
(Heat exchanger liquid pipe)
Used to detect liquid pipe temperature.
(15)
R5T
Thermistor
(Subcooling heat exchanger
liquid pipe)
Used to detect liquid pipe temperature of the subcooling heat exchanger.
(16)
R6T
Thermistor
(Subcooling heat exchanger
gas pipe)
Used to detect the gas pipe temperature on evaporation side of the heat
exchanger, keep the superheating degree at the heat exchanger constant,
and for other purposes.
(17)
R7T
Thermistor
(Heat exchanger deicer)
Used to detect liquid pipe temperature of air heat exchanger and for other
purposes.
(18)
R8T
Thermistor (Compressor
body)
Detects compressor surface temperature to stop operation at the surface
temperature of 120°C or more.
Содержание VRV S RXQ4/5ARV1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...