15 Relocation

Installation and operation manual

36

RXYSQ6TMYFK

VRV IV-S system air conditioner

4P524881-1 – 2018.02

14.2.7

Symptom: The user interface display
reads "U4" or "U5" and stops, but then
restarts after a few minutes

This is because the user interface is intercepting noise from electric
appliances  other  than  the  air  conditioner.  The  noise  prevents
communication  between  the  units,  causing  them  to  stop.  Operation
automatically restarts when the noise ceases.

14.2.8

Symptom: Noise of air conditioners
(Indoor unit)

▪ A  "zeen"  sound  is  heard  immediately  after  the  power  supply  is

turned  on.  The  electronic  expansion  valve  inside  an  indoor  unit
starts  working  and  makes  the  noise.  Its  volume  will  reduce  in
about one minute.

▪ A  continuous  low  "shah"  sound  is  heard  when  the  system  is  in

cooling  operation  or  at  a  stop.  When  the  drain  pump  (optional
accessories) is in operation, this noise is heard.

▪ A  "pishi-pishi"  squeaking  sound  is  heard  when  the  system  stops

after heating operation. Expansion and contraction of plastic parts
caused by temperature change make this noise.

▪ A low "sah", "choro-choro" sound is heard while the indoor unit is

stopped.  When  another  indoor  unit  is  in  operation,  this  noise  is
heard. In order to prevent oil and refrigerant from remaining in the
system, a small amount of refrigerant is kept flowing.

14.2.9

Symptom: Noise of air conditioners
(Indoor unit, outdoor unit)

▪ A  continuous  low  hissing  sound  is  heard  when  the  system  is  in

cooling  or  defrost  operation.  This  is  the  sound  of  refrigerant  gas
flowing through both indoor and outdoor units.

▪ A  hissing  sound  which  is  heard  at  the  start  or  immediately  after

stopping  operation  or  defrost  operation.  This  is  the  noise  of
refrigerant caused by flow stop or flow change.

14.2.10 Symptom: Noise of air conditioners

(Outdoor unit)

When the tone of operating noise changes. This noise is caused by
the change of frequency.

14.2.11 Symptom: Dust comes out of the unit

When  the  unit  is  used  for  the  first  time  in  a  long  time.  This  is
because dust has gotten into the unit.

14.2.12 Symptom: The units can give off odours

The  unit  can  absorb  the  smell  of  rooms,  furniture,  cigarettes,  etc.,
and then emit it again.

14.2.13 Symptom: The outdoor unit fan does not

spin

During  operation.  The  speed  of  the  fan  is  controlled  in  order  to
optimise product operation.

14.2.14 Symptom: The display shows "88"

This  is  the  case  immediately  after  the  main  power  supply  switch  is
turned  on  and  means  that  the  user  interface  is  in  normal  condition.
This continues for 1 minute.

14.2.15 Symptom: The compressor in the outdoor

unit does not stop after a short heating
operation

This is to prevent refrigerant from remaining in the compressor. The
unit will stop after 5 to 10 minutes.

14.2.16 Symptom: The inside of an outdoor unit is

warm even when the unit has stopped

This is because the crankcase heater is warming the compressor so
that the compressor can start smoothly.

14.2.17 Symptom: Hot air can be felt when the

indoor unit is stopped

Several  different  indoor  units  are  being  run  on  the  same  system.
When another unit is running, some refrigerant will still flow through
the unit.

15

Relocation

Contact  your  dealer  for  removing  and  reinstalling  the  total  unit.
Moving units requires technical expertise.

16

Disposal

This  unit  uses  hydrofluorocarbon.  Contact  your  dealer  when
discarding this unit.

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

Содержание VRV IV-S RXYSQ6TMYFK

Страница 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ6TMYFK...

Страница 2: ...0 1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB...

Страница 3: ...r unit installation 15 5 8 1 To finish the transmission wiring 15 6 Configuration 15 6 1 Making field settings 15 6 1 1 About making field settings 15 6 1 2 To access the field setting components 16 6...

Страница 4: ...part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing Format Paper in the box of the outdoor unit Outdoor unit in...

Страница 5: ...requirements of the outdoor unit in cold climates NOTICE When operating the unit in heating in a low outdoor ambient temperature with high humidity conditions make sure to take precautions to keep the...

Страница 6: ...to be increased More specifications can be found in the technical engineering data book a e b c d a Outdoor unit b Main pipes c Increase d First refrigerant branch kit e Indoor unit Outdoor unit capac...

Страница 7: ...h distance between outdoor and all indoors 600 m If the total transmission wiring exceeds these limits it may result in communication error 5 Installation 5 1 Opening the units 5 1 1 To open the outdo...

Страница 8: ...h into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning Result The valve is now open To fully open the 19 1 mm 25 4 mm stop valve...

Страница 9: ...ine stop valve A Valve A B Valve B 3 Recover gas and oil from the pinched piping by using a recovery unit CAUTION Do not vent gases into the atmosphere 4 When all gas and oil is recovered from the pin...

Страница 10: ...es after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor 5 4 Checking the refrigerant piping 5 4 1 About checking...

Страница 11: ...not see also the flow chart earlier described in this chapter see 5 4 1 About checking the refrigerant piping on page 10 5 4 4 To perform a leak test The leak test must satisfy the specifications of E...

Страница 12: ...n page 16 If a malfunction code is present see 8 1 Solving problems based on error codes on page 21 NOTICE Make sure all connected indoor units are recognised setting 1 10 NOTICE Close the front panel...

Страница 13: ...will start operation INFORMATION The manual refrigerant charge operation will automatically stop within 30 minutes If charging is not completed after 30 minutes perform the additional refrigerant char...

Страница 14: ...recautions when making knockout holes Avoid damaging the casing After making the knockout holes we recommend you remove the burrs and paint the edges and areas around the edges using repair paint to p...

Страница 15: ...nishing tape as shown in figure below a b c d e a Liquid pipe b Gas pipe c Insulator d Transmission wiring F1 F2 e Finishing tape 6 Configuration INFORMATION It is important that all information in th...

Страница 16: ...ting BS3 RETURN For field setting Display The display gives feedback about the field settings which are defined as Mode Setting Value The display is a 7 segments display Example Description Default si...

Страница 17: ...ow noise operation reduces the sound generated by the unit compared to nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of th...

Страница 18: ...en an external signal is sent to the unit this setting should be changed This setting will only be effective when the optional external control adaptor DTA104A61 62 is installed in the indoor unit 0 d...

Страница 19: ...stem needs to be running under power consumption limitation conditions when an external signal is sent to the unit this setting defines the level power consumption limitation that will be applied for...

Страница 20: ...ccording to the instructions described in the chapter 5 7 Connecting the electrical wiring on page 14 according to the wiring diagrams and according to the applicable legislation Power supply voltage...

Страница 21: ...more The unit will start test operation Result The test operation is automatically carried out the outdoor unit display will indicate and the indication Test operation and Under centralised control w...

Страница 22: ...expansion valve malfunction subcool Y2E A1P X21A Check connection on PCB or actuator Electronic expansion valve malfunction main Y1E A1P X23A Check connection on PCB or actuator Discharge temperature...

Страница 23: ...t run abnormal ending Execute test run again Warning faulty wiring to Q1 Q2 Check Q1 Q2 wiring Malfunction code faulty wiring to Q1 Q2 Check Q1 Q2 wiring Too many indoor units are connected to F1 F2 l...

Страница 24: ...5 28 88 100 154 53 22 98 80 19 95 53 626 633 89 3D083088A f f g a b d h f c e i j a Gas pipe connection brazing 22 2 b Liquid pipe connection brazing 9 5 c Service port high pressure in the unit d Ser...

Страница 25: ...D Height of obstacles B and D 1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be inst...

Страница 26: ...high pressure i Check valve j Oil separator k Capillary tube 2 l Accumulator m Service port refrigerant charge M1C Compressor M1F M2F Fan motor R1T Thermistor air R21T Thermistor discharge R3T Thermi...

Страница 27: ...A1P F101U Fuse A4P A5P F411U F412U Fuse A2P F601U Fuse A3P HAP Light emitting diode service monitor is green A1P A3P A4P A5P K1M Magnetic contactor A3P K1R Magnetic relay A3P K3R Magnetic relay A3P K4...

Страница 28: ...8 36 Btu h W Power input 5 26 kW Cooling T2 Capacity 12 89 kW 44000 Btu h EER 7 78 Btu h W Power input 5 65 kW Heating maximum b Capacity 12 30 kW 42000 Btu h W COP 4 30 W W Power input 2 87 kW PED C...

Страница 29: ...onment For more details refer to sound level drawings in the technical data book Electrical specifications Specification RXYSQ6 Power supply Name YF Phase 3N Frequency 50 60 Hz Voltage 380 415 400 V C...

Страница 30: ...t Total capacity of indoor units needs to be within the specified range The connection ratio CR 100 CR 130 HP class of outdoor unit 100 minimum CR 130 maximum CR 6 140 182 NOTICE When selecting the to...

Страница 31: ...C WB Indoor temperature 21 32 C DB 14 25 C WB 15 27 C DB Indoor humidity 80 a a To avoid condensation and water dripping out of the unit If the temperature or the humidity is beyond these conditions s...

Страница 32: ...nd wall mounted Refer to 12 4 Adjusting the air flow direction on page 32 for details To stop 4 Press the ON OFF button on the user interface once again Result The operation lamp goes out and the syst...

Страница 33: ...ge If damaged the unit may fall and result in injury NOTICE Do not wipe the controller operation panel with benzine thinner chemical dust cloth etc The panel may get discoloured or the coating peeled...

Страница 34: ...bstacles and make sure the air can flow freely Check if the user interface display shows time to clean the air filter Refer to 13 Maintenance and service on page 33 and Maintenance in the indoor unit...

Страница 35: ...t overloading of the compressor motor the air conditioner starts 5 minutes after it is turned ON again in case it was turned OFF just before The same starting delay occurs after the operation mode sel...

Страница 36: ...ant caused by flow stop or flow change 14 2 10 Symptom Noise of air conditioners Outdoor unit When the tone of operating noise changes This noise is caused by the change of frequency 14 2 11 Symptom D...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...4P524881 1 2018 02 Copyright 2018 Daikin...

Отзывы: