5 Installation

Installation and operation manual

7

RXYSQ6TMYFK
VRV IV-S system air conditioner
4P524881-1 – 2018.02

Indoor unit capacity index

Refrigerant branch kit

x<200

KHRQ22M29H

INFORMATION

Maximum 8 branches can be connected to a header.

4.3

Preparing electrical wiring

4.3.1

Safety device requirements

The  power  supply  must  be  protected  with  the  required  safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage protector in accordance with the applicable legislation.

Selection and sizing of the wiring should be done in accordance with
the applicable legislation based on the information mentioned in the
table below.

Model

Minimum

circuit

ampacity

Recommended

fuses

Power supply

RXYSQ6

22 A

25 A

3N~ 50 / 60 Hz

380-415 / 400 V

Transmission wiring

Transmission wiring

Vinyl cords with 0.75 to

1.25 mm² sheath or cables

(2‑core wires)

Maximum wiring length

(= distance between outdoor and
furthest indoor unit)

300 m

Total wiring length

(= distance between outdoor and
all indoors)

600 m

If the total transmission wiring exceeds these limits, it may
result in communication error.

5

Installation

5.1

Opening the units

5.1.1

To open the outdoor unit

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING

5.2

Mounting the outdoor unit

5.2.1

To provide the installation structure

Prepare  4  sets  of  anchor  bolts,  nuts  and  washers  (field  supply)  as
follows:

(mm)

>150

620

(485-495)

490

4× M12

a

a

Make sure not to cover the drain holes.

5.2.2

To install the outdoor unit

4× M12

5.2.3

To provide drainage

▪ Make sure that condensation water can be evacuated properly.

▪ Install  the  unit  on  a  base  to  make  sure  that  there  is  proper

drainage in order to avoid ice accumulation.

▪ Prepare a water drainage channel around the foundation to drain

waste water away from the unit.

▪ Avoid  drain  water  flowing  over  the  footpath,  so  that  it  does  NOT

become slippery in case of ambient freezing temperatures.

▪ If  you  install  the  unit  on  a  frame,  install  a  waterproof  plate  within

150  mm  of  the  bottom  side  of  the  unit  in  order  to  prevent  water
from getting into the unit and to avoid drain water dripping (see the
following figure).

Содержание VRV IV-S RXYSQ6TMYFK

Страница 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ6TMYFK...

Страница 2: ...0 1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB...

Страница 3: ...r unit installation 15 5 8 1 To finish the transmission wiring 15 6 Configuration 15 6 1 Making field settings 15 6 1 1 About making field settings 15 6 1 2 To access the field setting components 16 6...

Страница 4: ...part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing Format Paper in the box of the outdoor unit Outdoor unit in...

Страница 5: ...requirements of the outdoor unit in cold climates NOTICE When operating the unit in heating in a low outdoor ambient temperature with high humidity conditions make sure to take precautions to keep the...

Страница 6: ...to be increased More specifications can be found in the technical engineering data book a e b c d a Outdoor unit b Main pipes c Increase d First refrigerant branch kit e Indoor unit Outdoor unit capac...

Страница 7: ...h distance between outdoor and all indoors 600 m If the total transmission wiring exceeds these limits it may result in communication error 5 Installation 5 1 Opening the units 5 1 1 To open the outdo...

Страница 8: ...h into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning Result The valve is now open To fully open the 19 1 mm 25 4 mm stop valve...

Страница 9: ...ine stop valve A Valve A B Valve B 3 Recover gas and oil from the pinched piping by using a recovery unit CAUTION Do not vent gases into the atmosphere 4 When all gas and oil is recovered from the pin...

Страница 10: ...es after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor 5 4 Checking the refrigerant piping 5 4 1 About checking...

Страница 11: ...not see also the flow chart earlier described in this chapter see 5 4 1 About checking the refrigerant piping on page 10 5 4 4 To perform a leak test The leak test must satisfy the specifications of E...

Страница 12: ...n page 16 If a malfunction code is present see 8 1 Solving problems based on error codes on page 21 NOTICE Make sure all connected indoor units are recognised setting 1 10 NOTICE Close the front panel...

Страница 13: ...will start operation INFORMATION The manual refrigerant charge operation will automatically stop within 30 minutes If charging is not completed after 30 minutes perform the additional refrigerant char...

Страница 14: ...recautions when making knockout holes Avoid damaging the casing After making the knockout holes we recommend you remove the burrs and paint the edges and areas around the edges using repair paint to p...

Страница 15: ...nishing tape as shown in figure below a b c d e a Liquid pipe b Gas pipe c Insulator d Transmission wiring F1 F2 e Finishing tape 6 Configuration INFORMATION It is important that all information in th...

Страница 16: ...ting BS3 RETURN For field setting Display The display gives feedback about the field settings which are defined as Mode Setting Value The display is a 7 segments display Example Description Default si...

Страница 17: ...ow noise operation reduces the sound generated by the unit compared to nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of th...

Страница 18: ...en an external signal is sent to the unit this setting should be changed This setting will only be effective when the optional external control adaptor DTA104A61 62 is installed in the indoor unit 0 d...

Страница 19: ...stem needs to be running under power consumption limitation conditions when an external signal is sent to the unit this setting defines the level power consumption limitation that will be applied for...

Страница 20: ...ccording to the instructions described in the chapter 5 7 Connecting the electrical wiring on page 14 according to the wiring diagrams and according to the applicable legislation Power supply voltage...

Страница 21: ...more The unit will start test operation Result The test operation is automatically carried out the outdoor unit display will indicate and the indication Test operation and Under centralised control w...

Страница 22: ...expansion valve malfunction subcool Y2E A1P X21A Check connection on PCB or actuator Electronic expansion valve malfunction main Y1E A1P X23A Check connection on PCB or actuator Discharge temperature...

Страница 23: ...t run abnormal ending Execute test run again Warning faulty wiring to Q1 Q2 Check Q1 Q2 wiring Malfunction code faulty wiring to Q1 Q2 Check Q1 Q2 wiring Too many indoor units are connected to F1 F2 l...

Страница 24: ...5 28 88 100 154 53 22 98 80 19 95 53 626 633 89 3D083088A f f g a b d h f c e i j a Gas pipe connection brazing 22 2 b Liquid pipe connection brazing 9 5 c Service port high pressure in the unit d Ser...

Страница 25: ...D Height of obstacles B and D 1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be inst...

Страница 26: ...high pressure i Check valve j Oil separator k Capillary tube 2 l Accumulator m Service port refrigerant charge M1C Compressor M1F M2F Fan motor R1T Thermistor air R21T Thermistor discharge R3T Thermi...

Страница 27: ...A1P F101U Fuse A4P A5P F411U F412U Fuse A2P F601U Fuse A3P HAP Light emitting diode service monitor is green A1P A3P A4P A5P K1M Magnetic contactor A3P K1R Magnetic relay A3P K3R Magnetic relay A3P K4...

Страница 28: ...8 36 Btu h W Power input 5 26 kW Cooling T2 Capacity 12 89 kW 44000 Btu h EER 7 78 Btu h W Power input 5 65 kW Heating maximum b Capacity 12 30 kW 42000 Btu h W COP 4 30 W W Power input 2 87 kW PED C...

Страница 29: ...onment For more details refer to sound level drawings in the technical data book Electrical specifications Specification RXYSQ6 Power supply Name YF Phase 3N Frequency 50 60 Hz Voltage 380 415 400 V C...

Страница 30: ...t Total capacity of indoor units needs to be within the specified range The connection ratio CR 100 CR 130 HP class of outdoor unit 100 minimum CR 130 maximum CR 6 140 182 NOTICE When selecting the to...

Страница 31: ...C WB Indoor temperature 21 32 C DB 14 25 C WB 15 27 C DB Indoor humidity 80 a a To avoid condensation and water dripping out of the unit If the temperature or the humidity is beyond these conditions s...

Страница 32: ...nd wall mounted Refer to 12 4 Adjusting the air flow direction on page 32 for details To stop 4 Press the ON OFF button on the user interface once again Result The operation lamp goes out and the syst...

Страница 33: ...ge If damaged the unit may fall and result in injury NOTICE Do not wipe the controller operation panel with benzine thinner chemical dust cloth etc The panel may get discoloured or the coating peeled...

Страница 34: ...bstacles and make sure the air can flow freely Check if the user interface display shows time to clean the air filter Refer to 13 Maintenance and service on page 33 and Maintenance in the indoor unit...

Страница 35: ...t overloading of the compressor motor the air conditioner starts 5 minutes after it is turned ON again in case it was turned OFF just before The same starting delay occurs after the operation mode sel...

Страница 36: ...ant caused by flow stop or flow change 14 2 10 Symptom Noise of air conditioners Outdoor unit When the tone of operating noise changes This noise is caused by the change of frequency 14 2 11 Symptom D...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...4P524881 1 2018 02 Copyright 2018 Daikin...

Отзывы: