9 Technical data
Installation and operation manual
28
RXYSQ6TMYFK
VRV IV-S system air conditioner
4P524881-1 – 2018.02
9.6
Technical specifications: Outdoor unit
Technical specifications
Specification
RXYSQ6
Casing material
Painted galvanised steel
Dimensions h×w×d
1615×940×460 mm
Weight
175 kg
Operation range
▪ Cooling (min./max.)
–5/52°C
▪ Heating (min./max.)
–20/15.5°C
Cooling T1
(a)
▪ Capacity
15.25 kW / 52000 Btu/h
▪ EER
11.42 Btu/h/W
▪ Power input
4.55 kW
Cooling T3
▪ Capacity
12.89 kW / 44000 Btu/h
▪ EER
8.36 Btu/h/W
▪ Power input
5.26 kW
Cooling T2
▪ Capacity
12.89 kW / 44000 Btu/h
▪ EER
7.78 Btu/h/W
▪ Power input
5.65 kW
Heating (maximum)
(b)
▪ Capacity
12.30 kW / 42000 Btu/h/W
▪ COP
4.30 W/W
▪ Power input
2.87 kW
PED
▪ Category
2
▪ Most critical part
Accumulator
▪ PS×V
279 bar×l
Maximum number of indoor units connected
(c)
64
Heat exchanger
▪ Type
Cross fin
▪ Treatment
Anti corrosion
Fan
▪ Type
Propeller
▪ Quantity
2
▪ Air flow rate
(d)
182 m³/min
▪ Motor
2
▪ Model
Direct drive
▪ Output/pcs
200 W
Compressor
▪ Quantity
1
▪ Model
Inverter
▪ Type
Hermetically sealed scroll compressor
▪ Crankcase heater
33 W
Sound level (nominal)
(e)
▪ Sound power
(f)
74 dBA
▪ Sound pressure
(g)
55 dBA
Refrigerant
▪ Type
R410A
▪ Charge
7 kg
Refrigerant oil
FVC68D
Содержание VRV IV-S RXYSQ6TMYFK
Страница 37: ......
Страница 38: ......
Страница 39: ......