background image

5 Installation

Installation and operation manual

10

RXYSQ6TMYFK

VRV IV-S system air conditioner

4P524881-1 – 2018.02

4

Do the following:

▪ Connect the liquid pipe (a) to the liquid stop valve. (brazing)
▪ Connect the gas pipe (b) to the gas stop valve. (brazing)

a

b

NOTICE

When brazing:

 First braze the liquid side piping, then the

gas  side  piping.  Enter  the  electrode  from  the  front  of  the
unit and the welding torch from the right side to braze with
the flames facing outside and avoid the compressor sound
insulation and other piping.

a b

c

a

b f

g

c

d

e

A

A

a

 Electrode

b

 Burning-resistant plate

c

 Welding torch

d

 Flames

e

 Compressor sound insulation

f

 Liquid side piping

g

 Gas side piping

▪ Connect  the  gas  piping  accessories  (c,  d),  and  cut  them  to

the required length (d1).

Possibility 1: To the front

c

d

d1

Possibility 2: To the back

d

c

Possibility 3: To the side

c d d1

Possibility 4: Downwards

d

d1

5

Reattach the service cover and the piping intake plate.

6

Seal  all  gaps  (example:  a)  to  prevent  snow  and  small  animals
from entering the system.

a

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

5.4

Checking the refrigerant piping

5.4.1

About checking the refrigerant piping

Refrigerant piping works are 

finished?

The indoor units and/or 

outdoor unit were already 

powered ON?

Use procedure:
"Method 2: After power ON".

Finish piping work.

Use procedure:
"Method 1: Before power ON 

(regular method)".

Yes

No

No

Yes

It is very important that all refrigerant piping work is done before the
units (outdoor or indoor) are powered on.

When the units are powered on, the expansion valves will initialise.
This means that they will close. Leak test and vacuum drying of field
piping and indoor units is impossible when this happens.

Therefore,  there  will  be  explained  2  methods  for  initial  installation,
leak test and vacuum drying.

Method 1: Before power ON

If  the  system  has  not  yet  been  powered  on,  no  special  action  is
required to perform the leak test and the vacuum drying.

Method 2: After power ON

If  the  system  has  already  been  powered  on,  activate  setting  [2‑21]
(refer  to 

"6.1.4  To  access  mode  1  or  2"  on  page  16

).  This  setting

will  open  field  expansion  valves  to  guarantee  a  R410A  piping
pathway  and  make  it  possible  to  perform  the  leak  test  and  the
vacuum drying.

NOTICE

Make  sure  that  all  indoor  units  connected  to  the  outdoor
unit are powered on.

NOTICE

Wait  until  the  outdoor  unit  has  finished  the  initialisation  to
apply setting [2‑21].

Содержание VRV IV-S RXYSQ6TMYFK

Страница 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ6TMYFK...

Страница 2: ...0 1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB...

Страница 3: ...r unit installation 15 5 8 1 To finish the transmission wiring 15 6 Configuration 15 6 1 Making field settings 15 6 1 1 About making field settings 15 6 1 2 To access the field setting components 16 6...

Страница 4: ...part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing Format Paper in the box of the outdoor unit Outdoor unit in...

Страница 5: ...requirements of the outdoor unit in cold climates NOTICE When operating the unit in heating in a low outdoor ambient temperature with high humidity conditions make sure to take precautions to keep the...

Страница 6: ...to be increased More specifications can be found in the technical engineering data book a e b c d a Outdoor unit b Main pipes c Increase d First refrigerant branch kit e Indoor unit Outdoor unit capac...

Страница 7: ...h distance between outdoor and all indoors 600 m If the total transmission wiring exceeds these limits it may result in communication error 5 Installation 5 1 Opening the units 5 1 1 To open the outdo...

Страница 8: ...h into the stop valve and turn the stop valve counterclockwise 3 When the stop valve cannot be turned any further stop turning Result The valve is now open To fully open the 19 1 mm 25 4 mm stop valve...

Страница 9: ...ine stop valve A Valve A B Valve B 3 Recover gas and oil from the pinched piping by using a recovery unit CAUTION Do not vent gases into the atmosphere 4 When all gas and oil is recovered from the pin...

Страница 10: ...es after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor 5 4 Checking the refrigerant piping 5 4 1 About checking...

Страница 11: ...not see also the flow chart earlier described in this chapter see 5 4 1 About checking the refrigerant piping on page 10 5 4 4 To perform a leak test The leak test must satisfy the specifications of E...

Страница 12: ...n page 16 If a malfunction code is present see 8 1 Solving problems based on error codes on page 21 NOTICE Make sure all connected indoor units are recognised setting 1 10 NOTICE Close the front panel...

Страница 13: ...will start operation INFORMATION The manual refrigerant charge operation will automatically stop within 30 minutes If charging is not completed after 30 minutes perform the additional refrigerant char...

Страница 14: ...recautions when making knockout holes Avoid damaging the casing After making the knockout holes we recommend you remove the burrs and paint the edges and areas around the edges using repair paint to p...

Страница 15: ...nishing tape as shown in figure below a b c d e a Liquid pipe b Gas pipe c Insulator d Transmission wiring F1 F2 e Finishing tape 6 Configuration INFORMATION It is important that all information in th...

Страница 16: ...ting BS3 RETURN For field setting Display The display gives feedback about the field settings which are defined as Mode Setting Value The display is a 7 segments display Example Description Default si...

Страница 17: ...ow noise operation reduces the sound generated by the unit compared to nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of th...

Страница 18: ...en an external signal is sent to the unit this setting should be changed This setting will only be effective when the optional external control adaptor DTA104A61 62 is installed in the indoor unit 0 d...

Страница 19: ...stem needs to be running under power consumption limitation conditions when an external signal is sent to the unit this setting defines the level power consumption limitation that will be applied for...

Страница 20: ...ccording to the instructions described in the chapter 5 7 Connecting the electrical wiring on page 14 according to the wiring diagrams and according to the applicable legislation Power supply voltage...

Страница 21: ...more The unit will start test operation Result The test operation is automatically carried out the outdoor unit display will indicate and the indication Test operation and Under centralised control w...

Страница 22: ...expansion valve malfunction subcool Y2E A1P X21A Check connection on PCB or actuator Electronic expansion valve malfunction main Y1E A1P X23A Check connection on PCB or actuator Discharge temperature...

Страница 23: ...t run abnormal ending Execute test run again Warning faulty wiring to Q1 Q2 Check Q1 Q2 wiring Malfunction code faulty wiring to Q1 Q2 Check Q1 Q2 wiring Too many indoor units are connected to F1 F2 l...

Страница 24: ...5 28 88 100 154 53 22 98 80 19 95 53 626 633 89 3D083088A f f g a b d h f c e i j a Gas pipe connection brazing 22 2 b Liquid pipe connection brazing 9 5 c Service port high pressure in the unit d Ser...

Страница 25: ...D Height of obstacles B and D 1 Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be inst...

Страница 26: ...high pressure i Check valve j Oil separator k Capillary tube 2 l Accumulator m Service port refrigerant charge M1C Compressor M1F M2F Fan motor R1T Thermistor air R21T Thermistor discharge R3T Thermi...

Страница 27: ...A1P F101U Fuse A4P A5P F411U F412U Fuse A2P F601U Fuse A3P HAP Light emitting diode service monitor is green A1P A3P A4P A5P K1M Magnetic contactor A3P K1R Magnetic relay A3P K3R Magnetic relay A3P K4...

Страница 28: ...8 36 Btu h W Power input 5 26 kW Cooling T2 Capacity 12 89 kW 44000 Btu h EER 7 78 Btu h W Power input 5 65 kW Heating maximum b Capacity 12 30 kW 42000 Btu h W COP 4 30 W W Power input 2 87 kW PED C...

Страница 29: ...onment For more details refer to sound level drawings in the technical data book Electrical specifications Specification RXYSQ6 Power supply Name YF Phase 3N Frequency 50 60 Hz Voltage 380 415 400 V C...

Страница 30: ...t Total capacity of indoor units needs to be within the specified range The connection ratio CR 100 CR 130 HP class of outdoor unit 100 minimum CR 130 maximum CR 6 140 182 NOTICE When selecting the to...

Страница 31: ...C WB Indoor temperature 21 32 C DB 14 25 C WB 15 27 C DB Indoor humidity 80 a a To avoid condensation and water dripping out of the unit If the temperature or the humidity is beyond these conditions s...

Страница 32: ...nd wall mounted Refer to 12 4 Adjusting the air flow direction on page 32 for details To stop 4 Press the ON OFF button on the user interface once again Result The operation lamp goes out and the syst...

Страница 33: ...ge If damaged the unit may fall and result in injury NOTICE Do not wipe the controller operation panel with benzine thinner chemical dust cloth etc The panel may get discoloured or the coating peeled...

Страница 34: ...bstacles and make sure the air can flow freely Check if the user interface display shows time to clean the air filter Refer to 13 Maintenance and service on page 33 and Maintenance in the indoor unit...

Страница 35: ...t overloading of the compressor motor the air conditioner starts 5 minutes after it is turned ON again in case it was turned OFF just before The same starting delay occurs after the operation mode sel...

Страница 36: ...ant caused by flow stop or flow change 14 2 10 Symptom Noise of air conditioners Outdoor unit When the tone of operating noise changes This noise is caused by the change of frequency 14 2 11 Symptom D...

Страница 37: ......

Страница 38: ......

Страница 39: ......

Страница 40: ...4P524881 1 2018 02 Copyright 2018 Daikin...

Отзывы: