IM 1119-1
13
www.DaikinApplied.com
RCN Configuration Table for All WSHP Units
= WSHP Configuration
D4
Flash
Count
Function Selection
D3
Flash
Count
Description
Table 1 - Control Mode
1
WSHP
1
Fan will speed-hunt in AUTO. Fan speed 1, 2, or 3 may be manually selected to run continuously at that
selected speed.
Heat Pump
3
Fan will speed-hunt in Auto. Fan speed 1, 2 or 3 may be manually selected to run continuously at that
selected speed. Only control mode where O/B terminal will ever be energized
.
Table 2 - Short Cycle
2
Short Cycle - Active
1
The “Y” terminal/control line output signal is delayed by 3-minutes after a compressor run cycle or upon unit
power-up
Short Cycle - Inactive
2
The “Y” terminal/control line output signal is allowed to energize immediately after a compressor run cycle or
upon unit power-up
.
Table 3 - Fan Speed
3
Fan Speed 1 Only
1
Fan will speed-hunt in AUTO. Fan speed 1 or 2 may be selected to run continuously.
Fan Speeds 1 and 2 Enabled
2
Fan will speed-hunt in AUTO. Fan speed 1, 2 or 3 may be selected to run continuously.
Fan Speeds 1, 2 & 3 Enabled
3
Fan speed 1, 2 or 3 may be manually selected to run, continuously at that speed.
Hi/Low Fan Speed Operation
4
Fan speed 1 = Low, Fan speed 2 = High